All installations and services must be performed by qualified service personnel.
 
 15
 
 
 
F.  CLOSET INSTALLATION 
 
?
?
?
?
 WARNING:
 
HAZARD OF 
ASPHYXIATION: A suction 
effect will occur when the 
furnace is operating inside the 
closet with the closet door 
closed.  For proper operation, 
the furnace blower shall create 
no more than a 0.05-inch water 
column pressure differential 
between the closet and the 
adjoining space. 
                                         
 
 
 
 
 
 
 
 
 
 
 
 
                                                                                                  
 
                                                                                                
 
 
                                                                                              
Figure 5 
 
1.  The return air opening into the closet is to have a minimum free area of 250 square 
inches, (refer to Figure 5).
 
 
2.  The return air opening may be located in the top, the center or (ideally) the bottom of 
the closet door, or sidewall.  
 
Do not obstruct any return air openings, including the return grille on 
the furnace.  To do so may cause the furnace to activate the high temperature 
limit and shutdown, or it may cause asphyxiation. 
 
3. The cross-sectional area of the return air grille leading into the closet (when located   
     in the floor or ceiling) shall not be less than 250 square inches.