Installation – 
Mounting Height & Clearance
6
www.zephyronline.com
DUCTING
A minimum of 6” round duct must be used to 
maintain maximum air fl ow effi ciency.
Always use rigid type metal ducts only. Flexible 
ducts could restrict air fl ow by up to 50%.
Use calculation worksheet to compute total duct 
work (Page 5).
ALWAYS, when possible, reduce the number of 
transitions and turns. If a long duct run is required, 
increase duct size from 6” to 7” or 8”.
If turns or transitions are required: Install as far 
away from duct opening and as far apart between 
the two transitions as possible.
Minimum mount height between range top to hood 
bottom should be no less than 26”.
Maximum mount height should be no higher than 
34”.
It is important to install the hood at the proper 
mounting height. Hoods mounted too low could 
result in heat damage and fi re hazard; while hoods 
mounted too high will be hard to reach and will 
loose performance and effi ciency.
If available, also refer to range manufacturer’s 
height clearance requirements and recommended 
hood mounting height above range. Always check 
your local codes for any differences.
Duct cover extension kit available for ceiling 
heights up to 12 feet. Turn to page 19 for part 
number and ordering information.
DAMAGE-SHIPMENT / INSTALLATION:
•  Please fully inspect unit for damage before 
installation.
•  If the unit is damaged in shipment, return the 
unit to the store in which it was bought for 
repair or replacement.
•  If the unit is damaged by the customer, repair 
or replacement is the responsibility of the 
customer.
•  If the unit is damaged by the installer (if other 
than the customer), repair of replacement must 
be made by arrangement between customer 
and installer.
26” min.
34” max.
min.  A
min.  B
max. C
min.  D
min.  E
max. F
    
 
 
 
Standard  
Extension
Hood Heights  
 
Duct Cover 
Duct Cove
r
            minimum ducted (A)  28” 
 
45-
1/2
 minimum recirculating (B)  32” 
 
50“
                          maximum (C)  45” 
 
80”
Ceiling Heights
           minimum ducted (D)  90” (7’ 6”) 
107-
1/2
“ (9‘)
 minimum recirculating (E)  94” (7’ 10”) 
112“ (9‘ 4”)
                          maximum (F)  115” (9’ 7“)        150” (12’ 6”)
36”