OceanAire OWC3632 操作ガイド

ページ / 22
PROBLEM: WATER LEAKING FROM PAN 
 
1. (CAUSE) Leaky drain pan 
 
(REMEDY) Locate leak and repair pan. 
 
2. (CAUSE) Loose evaporator, drain or condensate pump hose 
 
(REMEDY) Tighten connections. 
 
3. (CAUSE) Defective condensate pump or excessive lift on pump 
 
(REMEDY) Examine to see if elevation exceeds 20 ft. (if it does, a larger pump will be required). 
Otherwise, change pump if defective. Pump will operate properly against 20 ft. of water total head pressure 
on pump. If combination of vertical height and horizontal drain line exceeds 20 ft. of water pressure drop, 
problems will occur. 
 
                                                                 PREVENTIVE MAINTENANCE 
 
AquaCooler  Series air conditioners are designed to last a long time and to give maximum performance and 
reliability with minimum maintenance. To prolong the life of the unit, regular maintenance must be 
performed as specified below: 
 
1. BLOWER MOTOR 
 
The OWC24 and 36 motor should be oiled every six months with SAE 20 non-detergent oil. The oil ports 
on the motor are visible. 
15