Movincool CLASSICPLUS14 サービスマニュアル

ページ / 66
Repair Section
32
7.2 Self-Diagnostic Codes
• Self-diagnostic codes are displayed on the control board under the following conditions and
clear method is as follows.
LCD Display
Description
Condition
Reset/Remedy
Drain tank is full
When the drain tank is filled with 
drain water. 
(“TANK FL” LED flashes and signal 
output (J106) turns on.)
1) Drain away. 
(LCD indicates “TANK”)
2) Press ON/OFF button.
Condensate pump 
problem
When (optional) condensate pump 
is damaged or broken. 
(J8 input of relay board turns to 
open and signal output (J106) turns 
on.)
1) Fix the condensate pump.
2) Reset the system.
To RESET: Press ON/OFF and 
HI/LO buttons on the control box 
simultaneously for 5 sec. 
Defect (short or open)
of room thermistor
When room thermistor (connecting
to J101) becomes short or open. 
(Signal output (J106) turns on.)
Disconnect and reconnect the 
room thermistor.
If it doesn’t work, then change it.
Defect (short or open) 
of freeze protection 
thermistor
When freeze protection thermistor
(connecting to J102) becomes short
or open. 
(Signal output (J106) turns on.)
Disconnect and reconnect the 
freeze protection thermistor.
If it doesn’t work, then change it.
Show running hours
Press ON/OFF and 
V
 buttons 
simultaneously for 3 sec, total 
operation hours of compressor is 
indicated by 6-digit (hours).
Example in left: 807 h
After 5 sec., display goes back to 
normal mode.
TU
AM
F
SET TEMP
HI
ON
COOL
FAN
F
SET TEMP
HI
ON
COOL
FAN
F
SET TEMP
HI
ON
COOL
FAN
F
SET TEMP
HI
ON
COOL
FAN
F
SET TEMP
HI
ON
COOL
FAN