TROUBLESHOOTING GUIDE 
 
The following steps and procedures are recommended for correcting the problems 
indicated. In the event that the problem can not be corrected, service may be required.  
  
SERVICE SHOULD BE PERFORMED BY A QUALIFIED AIR CONDITIONING 
SERVICE TECHNICIAN 
 
PROBLEM: UNIT DOES NOT POWER UP 
 
CAUSE:   Power interruption 
 
REMEDY: Check LCDI (on models with LCDI), and reset LCDI.  Check external power 
supply making sure that the disconnect is ON.  Check for blown fuses or tripped circuit 
breakers. Reset or replace if needed. 
 
CAUSE:  Loose display cable 
 
REMEDY:  Re-seat display cable at display and power module. 
 
CAUSE:  Phase Monitor Fault (3-Phase Models) 
 
REMEDY:  Check Phase Monitor, and correct power problem> 
 
 
PROBLEM: EVAPORATOR FAN RUNS BUT COMPRESSOR AND CONDENSER 
FAN DO NOT START 
 
CAUSE:  SET POINT — setting may be too high for cooling or too low for heating.   
REMEDY:  Make sure set-point is adjusted accordingly. You should see a red dot to 
the right of the temperature display indicating compressor ON. 
 
Note—there is a time delay for the compressor 
 
CAUSE: Loose Display Cable 
REMEDY:  Examine the control unit for loose wires. Tighten any loose connections.  
 
CAUSE:  Condition Alarm—”CON”. 
REMEDY:  Check condensate tank and empty tank or check condensate pump and 
make sure pump is working properly and that there is no kink in the drain line from the 
pump.   
 
CAUSE:  High Pressure Cut-Out—”CON” 
Check High Pressure Cut-out Switch.  
Press Reset and clear away any obstructions to the condenser intake or condenser 
discharge.   
 
CAUSE: Compressor contactor open or burned.      
REMEDY: Replace contactor 
 
CAUSE:  Defective Power Module 
REMEDY:  Replace Power Module. 