WineMate Wine Cooling Unit - Top Exhaust マニュアル

ページ / 3
dIXEL
Installing and Operating Instructions 
1592020032
 
 
Vinotemp XR30CX.doc Vinotemp 
XR30CX 
1/3 
Digital controller with off cycle defrost and  
Fan Control
 
XR30CX 
 
CONTENTS 
1.
 
GENERAL WARNING ____________________________________________________1
 
2.
 
GENERAL DESCRIPTION ________________________________________________1
 
3.
 
CONTROLLING LOADS __________________________________________________1
 
4.
 
FRONT PANEL COMMANDS ______________________________________________1
 
5.
 
MAX & MIN TEMPERATURE MEMORIZATION _______________________________1
 
6.
 
MAIN FUNCTIONS ______________________________________________________2
 
7.
 
PARAMETERS _________________________________________________________2
 
9.
 
TTL SERIAL LINE – FOR MONITORING SYSTEMS____________________________2
 
11.
 
INSTALLATION AND MOUNTING __________________________________________3
 
12.
 
ELECTRICAL CONNECTIONS _____________________________________________3
 
13.
 
HOW TO USE THE HOT KEY______________________________________________3
 
14.
 
ALARM SIGNALS _______________________________________________________3
 
15.
 
TECHNICAL DATA ______________________________________________________3
 
16.
 
CONNECTIONS_________________________________________________________3
 
17.
 
DEFAULT SETTING VALUES______________________________________________3
 
1.  GENERAL WARNING 
1.1  PLEASE READ BEFORE USING THIS MANUAL 
• 
This  manual  is  part  of  the  product  and  should  be  kept  near  the  instrument  for  easy  and 
quick reference. 
• 
The instrument shall not be used for purposes different from those described hereunder. It 
cannot be used as a safety device. 
• 
Check the application limits before proceeding. 
1.2 
 SAFETY PRECAUTIONS 
• 
Check the supply voltage is correct before connecting the instrument. 
• 
Do  not  expose  to  water  or  moisture:  use  the  controller  only  within  the  operating  limits 
avoiding sudden temperature changes with high atmospheric humidity to prevent  formation 
of condensation 
• 
Warning: disconnect all electrical connections before any kind of maintenance. 
• 
Fit  the  probe  where  it  is  not  accessible  by  the  End  User.  The  instrument  must  not  be 
opened. 
• 
In case of failure or faulty operation send the instrument back to the distributor or to “Dixell 
S.p.A.” (see address) with a detailed description of the fault. 
• 
Consider the maximum current which can be applied to each relay (see Technical Data). 
• 
Ensure that the wires for probes, loads and the power supply are separated and far enough 
from each other, without crossing or intertwining. 
• 
In case of applications in industrial environments, the use of mains filters (our mod. FT1) in 
parallel with inductive loads could be useful. 
2.  GENERAL DESCRIPTION 
Model  XR30CX,  format  32  x  74  mm,  is  a  digital  thermostat  with  off  cycle  defrost  designed  for 
refrigeration  applications  at  normal  temperature.  It  provides  two  relay  outputs,  one  for  the 
compressor, the other one can be used as light, for alarm signalling or as auxiliary output.. It is 
also provided with 1 or 2 NTC probe inputs the first one for temperature control, the second one, 
optional, to connect to the HOT KEY terminals to signal the condenser temperature alarm or to 
display a temperature. The digital input can operate as third temperature probe. 
The HOT KEY output allows to connect the unit, by means of the external module XJ485-CX,  to 
a network line ModBUS-RTU compatible such as the dIXEL
monitoring units  of X-WEB family. 
It allows to program the controller by means the HOT KEY programming keyboard.  
The instrument is fully configurable through special parameters that can  be easily programmed 
through the keyboard. 
3.  CONTROLLING LOADS 
3.1  COMPRESSOR 
The 
regulation 
is 
performed 
according  to  the  temperature 
measured  by  the  thermostat  probe 
with  a  positive  differential  from  the 
set  point:  if  the  temperature 
increases and reaches set point plus 
differential  the  compressor  is  started 
and  then  turned  off  when  the 
temperature  reaches  the  set  point 
value again. 
Time
Temper.
Compr.
SET
ON
 
In case of fault in the thermostat probe the start and stop of the compressor are timed through 
parameters “COn” and “COF”. 
3.2  DEFROST  
Defrost  is  performed  through  a  simple  stop  of  the  compressor.  Parameter  “IdF”  controls  the 
interval between defrost cycles, while its length is controlled by parameter “MdF”. 
4.  FRONT PANEL COMMANDS 
 
 
: To display target set point; in programming mode it selects a parameter or confirm an 
operation. 
  (DEF) To start a manual defrost 
 
 (UP): To see the max. stored temperature; in programming mode it browses the parameter 
codes or increases the displayed value. 
  (DOWN)  To  see  the  min  stored  temperature;  in  programming  mode  it  browses  the 
parameter codes or decreases the displayed value. 
O/I 
  To turn ON or OFF the controller (if enabled)  
 
KEY COMBINATIONS: 
  
 
  
To lock & unlock the keyboard. 
 
+
  
 
To enter in programming mode. 
  
+
  
To return to the room temperature display. 
 
4.1  CONTROL OF EVAPORATOR FANS 
The fan control mode is selected by means of the “FnC” parameter: 
FnC = C_n:  fans will switch ON and OFF with the compressor and not run during defrost; 
FnC = o_n  fans will run even if the compressor is off, and not run during defrost; 
After  defrost,  there  is  a  timed  fan  delay  allowing  for  drip  time,  set  by  means  of  the  “Fnd” 
parameter. 
FnC = C_Y   fans will switch ON and OFF with the compressor and run during defrost; 
FnC = o_Y  fans will run continuously also during defrost 
 
An  additional  parameter  “FSt”  provides  the  setting  of  temperature,  detected  by  the  evaporator 
probe, above which the fans are always OFF. This is used to make sure circulation of air only if 
his temperature is lower than set in “FSt”. 
4.1.1  Cyclical activation of the fans with compressor off. 
When  Fnc  =  c-n  or  c-Y  (fans  in  parallel  to  the  compressor),  by  means  of  the  Fon  and  FoF 
parameters the fans can carry out on and off cycles even if the compressor is switched off. When 
the compressor is stopped the fans go on working for the Fon time. With Fon =0 the fans remain 
always off, when the compressor is off. This increases humidity in the system. 
 
4.2  USE OF LEDS 
Each LED function is described in the following table. 
LED 
MODE 
FUNCTION 
 
ON 
Compressor enabled 
 
Flashing 
Anti-short cycle delay enabled 
 
ON 
Defrost enabled 
 
ON 
An alarm is occurring 
°C/°F  ON 
Measurement unit 
°C/°F  Flashing 
Programming phase 
 
 
 
 
 
 
 
 
 
 
 
 
5.  MAX & MIN TEMPERATURE MEMORIZATION 
5.1  HOW TO SEE THE MIN TEMPERATURE 
1.  
Press and release the n key. 
2.  
The “Lo” message will be displayed followed by the minimum temperature recorded. 
3.  
By pressing the n key again or by waiting 5s the normal display will be restored.