Installing and Operating Instructions 
1592020032
 
 
Vinotemp XR30CX.doc Vinotemp 
XR30CX 
3/3 
10.  INSTALLATION AND MOUNTING 
 
Instrument XR30CX shall be mounted on vertical panel, in a 
29x71 mm hole, and fixed using the special bracket supplied.  
The  temperature  range  allowed  for  correct  operation  is32  - 
140  °F.  Avoid  places  subject  to  strong  vibrations,  corrosive 
gases,  excessive  dirt  or  humidity.  The  same 
recommendations  apply  to  probes.  Let  air  circulate  by  the 
cooling holes. 
 
11.  ELECTRICAL CONNECTIONS 
The instrument is provided with screw terminal block to connect cables with a cross section up to 
2,5 mm
2
. Before connecting cables make sure the power supply complies with the instrument’s 
requirements. Separate the probe cables from the power supply cables, from the outputs and the 
power  connections.  Do  not  exceed  the  maximum  current  allowed  on  each  relay,  in  case  of 
heavier loads use a suitable external relay. 
11.1  PROBE CONNECTION 
The  probes  shall  be  mounted  with  the  bulb  upwards  to  prevent  damages  due  to  casual  liquid 
infiltration. It is recommended to place the thermostat probe away from air streams to correctly 
measure  the  average  room  temperature.  Place  the  defrost  termination  probe  among  the 
evaporator  fins  in  the  coldest  place,  where  most  ice  is  formed,  far  from  heaters  or  from  the 
warmest place during defrost, to prevent premature defrost termination. 
12.  HOW TO USE THE HOT KEY  
12.1  HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD) 
1. 
Program one controller with the front keypad. 
2. 
When the controller is ON, insert the “Hot key” and push o key; the  "uPL"  message 
appears followed a by flashing “End” 
3. 
Push “SET” key and the End will stop flashing. 
4. 
Turn OFF the instrument remove the “Hot Key”, then turn it ON again. 
 
NOTE: the “Err” message is displayed for failed programming. In this case push again o key if 
you want to restart the upload again or remove the “Hot key” to abort the operation. 
12.2  HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD) 
1. 
Turn OFF the instrument. 
2. 
Insert  a programmed “Hot Key” into the 5 PIN receptacle and then turn the Controller 
ON. 
3. 
Automatically  the  parameter  list  of  the  “Hot  Key”  is  downloaded  into  the  Controller 
memory, the “doL” message is blinking followed a by flashing “End”. 
4. 
After 10 seconds the instrument will restart working with the new parameters.  
5. 
Remove the “Hot Key”.
 
NOTE the message  “Err” is displayed for failed programming. In this case turn the unit off and 
then on if you want to restart the download again or remove the “Hot key” to abort the operation. 
13.  ALARM SIGNALS 
Message  
Cause 
Outputs 
“P1” 
Room probe  failure 
Compressor output acc. to par. “Con” and 
“COF” 
“HA” 
Maximum temperature alarm 
Outputs unchanged. 
“LA”  
Minimum temperature alarm 
Outputs unchanged. 
“CA”  
Serious external alarm 
(i1F=bAL) 
All outputs OFF. 
13.1  ALARM RECOVERY  
Probe alarms P1”, start a few seconds after the fault in the related probe; they automatically stop 
a few seconds after the probe restarts normal operation. Check connections before replacing the 
probe. Temperature alarms “HA”, “LA” automatically stop as soon as the temperature returns to 
normal value. 
Alarm “CA” (with i1F=PAL) recovers only by switching off and on the instrument. 
13.2  OTHER MESSAGES 
Pon 
Keyboard unlocked. 
PoF 
Keyboard locked 
noP 
In programming mode: none parameter is present in Pr1 
On the display or in dP2, dP3, dP4: the selected probe is nor enabled 
noA 
None alarm is recorded. 
14.  TECHNICAL DATA 
Housing: self extinguishing ABS. 
Case: XR30CX 
frontal 32x74 mm; depth 60mm; 
Mounting: XR30CX panel mounting in a 71x29mm panel cut-out 
Protection: IP20; Frontal protection: XR30CX IP65 
Connections: Screw terminal block ≤ 2,5 mm
2
 wiring. 
Power supply: 110Vac ±10%, 50/60Hz 
Power absorption: 3VA max 
Display
: 3 digits, red LED, 14,2 mm high; Inputs: Up to 3 NTC. 
Digital input:  free voltage contact 
Relay outputs: compressor SPST 16A/96A 250Vac FAN: SPDT 8(3) A, 250Vac 
Data storing: on the non-volatile memory (EEPROM). 
Kind of action: 1B; Pollution grade: 2;Software class: A.;  
Rated impulsive voltage: 2500V; Overvoltage Category: II 
Operating temperature: 
0÷60 °C;Storage temperature: -30÷85 °C.  
Relative humidity: 20÷85% (no condensing) 
Measuring and regulation range: NTC probe: -40÷110°C (-40÷230°F);  
Resolution: 0,1 °C or 1°C or 1 °F (selectable); Accuracy (ambient temp. 25°C):  ±0,7 °C ±1 
digit 
15.  CONNECTIONS 
15.1  XR30CX – 16A COMPRESSOR 
 
 
120Vac supply: connect to the terminals 7 and 8. 
 
16.  DEFAULT SETTING VALUES  
Label 
Name 
Range 
°F 
 
Set  Set point 
LS÷US 
55 
- - - 
Hy  Differential 
0,1÷25.5°C/ 1÷ 255°F 
Pr2 
LS  Minimum set point 
-50°C÷SET/-58°F÷SET 
50 
Pr2 
US  Maximum set point 
SET÷110°C/ SET ÷ 230°F 
65 
Pr2 
Ot  Thermostat probe calibration 
-12÷12°C /-120÷120°F 
Pr2 
COn  Compressor  ON  time  with  faulty 
probe 
0 ÷ 255 min 
15 
Pr2 
COF  Compressor  OFF  time  with  faulty 
probe 
0 ÷ 255 min 
30 
Pr2 
CF  Temperature measurement unit 
°C ÷ °F 
°F 
Pr2 
rES  Resolution (only in °C) 
in=integer; dE= dec.point
 
in 
Pr2 
dLy  Display temperature delay   
0 ÷ 20.0 min  (10 sec.)  
1:00 
Pr2 
IdF  Interval between defrost cycles 
1 ÷ 120 hours 
24 
Pr2 
MdF  (Maximum) length for defrost 
0 ÷ 255 min 
30 
Pr2 
dFd  Displaying during defrost 
rt, it, SEt, DEF 
it 
Pr2 
dAd  MAX display delay after defrost 
0 ÷ 255 min 
30 
Pr2 
Fnc  Fan operating mode 
C-n, o-n, C-y, o-Y 
c-n 
Pr2 
Fon  Fan on time with compressor off 
0÷15 (min.) 
Pr2 
FoF  Fan off time with compressor off 
0÷15 (min.) 
15 
Pr2 
ALc  Temperat. alarms configuration 
rE= related to set; 
Ab = absolute 
rE 
Pr2 
ALU  MAXIMUM temperature alarm 
Set÷110.0°C; Set÷230°F 
10 
Pr1 
ALL  Minimum temperature alarm 
-50.0°C÷Set/ -58°F÷Set 
10 
Pr1 
AFH  Differential for temperat. alarm 
recovery 
(0,1°C÷25,5°C) (1°F÷45°F) 
Pr2 
ALd  Temperature alarm delay 
0 ÷ 255 min 
120 
Pr2 
Adr  Serial address 
0÷247 
Pr2 
onF  on/off key enabling 
nu, oFF; ES 
OFF 
Pr2 
dP1  Room probe display 
-- 
 -- 
Pr2 
rEL  Software release 
-- 
 -- 
Pr2 
Ptb  Map code 
-- 
 -- 
Pr2 
 
 
Dixell S.p.A.   
Distributed by: Weiss Instruments, Inc. 
905 Waverly Ave. Holtsville, NY 11742   631-207-1200  www.weissinstruments.com 