Omron CPM2B ユーザーズマニュアル

ページ / 149
6-2
Section
Programming Console Operations
97
2. To specify up-differentiation monitoring, press the SHIFT and then the Up
Arrow Key. The symbols “U@” will appear.
SHIFT
L000000001H0000
U@OFF^ OFF^ OFF
Indicates waiting for the bit to turn ON.
To specify down-differentiation monitoring, press the SHIFT and then the
Down Arrow Key. The symbols “D@” will appear.
SHIFT
L000000001H0000
D@OFF^ OFF^ OFF
3. The buzzer will sound when the specified bit goes from off to on (for up-dif-
ferentiation) or from on to off (for down-differentiation).
L000000001H0000
^  ON^ OFF^ OFF
Note The buzzer will not sound if it has been turned off.
4. Press the CLR Key to end differentiation monitoring and return to the normal
monitoring display.
CLR
L000000001H0000
^ OFF^ OFF^ OFF
6-2-14 Binary Monitor
This operation is used to monitor the ON/OFF status of any word’s 16 bits. It
is possible in any mode.
RUN
MONITOR
PROGRAM
OK
OK
OK
1, 2, 3...
1. Monitor the status of the desired word according to the procedure described
in 6-2-12 Bit, Digit, Word Monitor. The desired word should be leftmost on
the display if 2 or more words are being monitored.
(Word monitor)
 c010
 0000
2. Press the SHIFT and then the MONTR Key to begin binary monitoring. The
ON/OFF status of the selected word’s 16 bits will be shown along the bottom
of the display. A 1 indicates a bit is on, and a 0 indicates it is off.
SHIFT MONTR
     c010 MONTR
0000000000000000
Bit 15
Bit 00
The status of force-set bits is indicated by “S,” and the status of a force-reset
bits is indicated by “R,” as shown below.
Force-set bit
000S0000000R0000
Force-reset bit
    c010 MONTR
Note a) The status of displayed bits can be changed at this point. Refer to
6-2-21 Binary Data Modification for details.
b) The Up or Down Arrow Key can be pressed to display the status of
the previous or next word’s bits.