Omron CPM2B ユーザーズマニュアル

ページ / 149
6-2
Section
Programming Console Operations
105
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Press the SET and then the RESET Key. A confirmation message will ap-
pear.
SET
RESET
00000FORCE RELE?
Note If you mistakenly press the wrong key, press CLR and start again
from the beginning.
3. Press the NOT Key to clear the force-set/reset status of bits in all data areas.
NOT
00000FORCE RELE
END
6-2-26 Hex-ASCII Display Change
This operation is used to convert word data displays back and forth between
4-digit hexadecimal data and ASCII. It is possible in any mode.
The displayed PV of the timer or counter cannot be changed.
RUN
MONITOR
PROGRAM
OK
OK
OK
1, 2, 3...
1. Monitor the status of the desired word(s) according to the procedure de-
scribed in 6-2-12 Bit, Digit, Word Monitor. While the multiple addresses are
being monitored, the leftmost word is subject to change.
(Multiple address monitor)
D0000D0001
 4142 3031
2. Press the TR Key to switch to ASCII display. The display will toggle between
hexadecimal and ASCII displays each time the TR Key is pressed.
TR
D0000D0001
 "AB" 3031
TR
D0000D0001
 4142 3031
Note
1. A message contained in three words can be displayed by using ASCII dis-
play in combination with the Three-word monitor operation.
2. The Hexadecimal, BCD Data Modification Operation can be used while dis-
playing ASCII data. Input values in 4-digit hexadecimal.
6-2-27 Displaying the Cycle Time
This operation is used to display the current average cycle time (scan time).
It is possible only in RUN or MONITOR mode while the program is being
executed.
RUN
MONITOR
PROGRAM
OK
OK
No
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Press the MONTR Key to display the cycle time.
MONTR
00000SCAN TIME
         012.1MS
“MS” in the display indicates
the unit “ms” for the cycle time.
There might be differences in displayed values when the MONTR Key is
pressed repeatedly. These differences are caused by changing execution
conditions.