Omron CPM2B ユーザーズマニュアル

ページ / 149
3-5
Section
Wiring and Connections
42
3-5-2 I/O Wiring Procedures
Removing and Wiring I/O Terminal Blocks
The following tables provide output terminal block specifications.
CPU Boards and Expansion I/O Boards
with relay outputs
Output terminal blocks
Item
Specification
Screw size
M3
Recommended tightening
torque
0.5 to 0.6 N
S
m
Recommended screwdriver: OMRON XW4E-00C
Item
Specification
Solid wire
0.2 to 2.5 mm
(AWG 24 to AWG12) (Strip 7 mm.)
Stranded wire (See notes.)
0.2 to 2.5 mm
2
 (AWG 24 to AWG12) (Strip 7 mm.)
Two-cond
Solid
×
 (0.2 to 1.0 mm
2
) (AWG 24 to AWG 20)
uctor
Stranded
×
 (0.2 to 1.5 mm
2
) (AWG 24 to AWG 16)
wires
Stranded with
pin terminal
×
 (0.25 to 1.0 mm
2
) (AWG 24 to AWG 20)
without an insulating sleeve
Pin terminals
0.2 to 2.5 mm
2
 diameter, 7-mm long pin terminal
Bridge (shorts terminals)
Terminal pitch 5.08 mm
Recommended Bridges:
OMRON XW4Z-02C (2 pole)
OMRON XW4Z-03C (3 pole)
Note
1. When using stranded wire, be sure to avoid stray wire strands that might
short-circuit an adjacent terminal.
2. Do not solder the ends of stranded wires. Solder can break and cause wiring
problems. Also, the solder can cause corrosion on the contact surface.
3. Be sure to use the correct pin allocation when assembling and wiring con-
nectors or terminal blocks.
Use the following procedure when wiring a terminal block.
1, 2, 3...
1. Use a flatblade screwdriver to loosen the screws at the left and right sides of
the terminal block.
Terminal Block
Specifications
Recommended Wire and
Terminals
Removing and Wiring a
Terminal Block