Omron CPM2B ユーザーズマニュアル

ページ / 149
4-5
Section
PC Setup
65
tive, and program execution will have to be restarted to make changes in
DM 6615 to DM 6644 effective.
If an incorrect PC Setup setting is accessed, a non-fatal error (error code 9B) will
be generated, the corresponding error flag (AR 1300 to AR 1302) will be turned
ON, and the default setting will be used instead of the incorrect setting.
4-5-2 PC Setup Settings
Word(s)
Bit(s)
Function
Startup Processing (DM 6600 to DM 6614)
The following settings are effective after transfer to the PC only after the PC is restarted.
DM 6600
00 to 07
Startup mode (effective when bits 08 to 15 are set to 02).
00: PROGRAM; 01: MONITOR; 02: RUN
08 to 15
Startup mode designation
00:
According to communications switch SW201 and peripheral port connection
(See table at the bottom of this page.)
01:  Continue operating mode last used before power was turned OFF.
02:
Setting in 00 to 07
DM 6601
00 to 07
Not used.
08 to 11
IOM Hold Bit (SR 25212) Status at Startup
0: Reset to 0; 1: Maintain previous status
12 to 15
Forced Status Hold Bit (SR 25211) Status at Startup
0: Reset to 0; 1: Maintain previous status
DM 6602
00 to 03
Program memory write-protection
0: Program memory unprotected
1: Program memory write-protected (except DM 6602 itself)
04 to 07
Programming Console display language
0: English; 1: Japanese
08 to 11
Expansion instruction function code assignments
0: Default settings
1: User assignments
12 to 15
Not used.
DM 6603
00 to 15
Not used.
DM 6604
00 to 07
00: A memory error will not be generated if data could not be retained by the battery.
01: A memory error will be generated if data could not be retained by the battery.
08 to 15
Not used.
DM 6605 to
DM 6614
00 to 15
Not used.
Note The startup operating mode will be as shown in the following table is bits 08 to 15
of DM 6600 are set to 00.
Peripheral port
Communications switch SW201
connected to
OFF
ON
Nothing
PROGRAM
RUN
Programming
Console
Mode set on Programming
Console mode switch
PROGRAM (The CPM2B will
not be able to communicate
with Programming Console.)
Other Programming
Device
PROGRAM (The CPM2B will
not be able to communicate
with Programming Device.)
PROGRAM
Word(s)
Bit(s)
Function
Cycle Time Settings (DM 6615 to DM 6619)
The following settings are effective after transfer to the PC the next time operation is started.
DM 6615
00 to 15
Not used.
Errors in the PC Setup