Omron CPM2B ユーザーズマニュアル

ページ / 149
!
!
!
!
!
!
!
5
Application Precautions
xiii
Emergency stop circuits, interlock circuits, limit circuits, and similar safety
measures must be provided in external control circuits.
The PC will turn OFF all outputs when its self-diagnosis function detects any
error or when a severe failure alarm (FALS) instruction is executed. As a coun-
termeasure for such errors, external safety measures must be provided to en-
sure safety in the system.
The PC outputs may remain ON or OFF due to deposition or burning of the
output relays or destruction of the output transistors. As a countermeasure for
such problems, external safety measures must be provided to ensure safety in
the system.
WARNING
When transferring programs to other nodes, or when making changes to I/O
memory, confirm the safety of the destination node before transfer. Not doing so
may result in injury.
Caution
Execute online edit only after confirming that no adverse effects will be caused
by extending the cycle time. Otherwise, the input signals may not be readable.
Caution
Tighten the screws on the terminal block to the torque specified in the operation
manual. The loose screws may result in burning or malfunction.
4
Operating Environment Precautions
Caution
Do not operate the control system in the following places:
Locations subject to direct sunlight.
Locations subject to temperatures or humidity outside the range specified in
the specifications.
Locations subject to condensation as the result of severe changes in tempera-
ture.
Locations subject to corrosive or flammable gases.
Locations subject to dust (especially iron dust) or salts.
Locations subject to exposure to water, oil, or chemicals.
Locations subject to shock or vibration.
Caution
Take appropriate and sufficient countermeasures when installing systems in the
following locations:
Locations subject to static electricity or other forms of noise.
Locations subject to strong electromagnetic fields.
Locations subject to possible exposure to radioactivity.
Locations close to power supplies.
Caution
The operating environment of the PC System can have a large effect on the lon-
gevity and reliability of the system. Improper operating environments can lead to
malfunction, failure, and other unforeseeable problems with the PC System. Be
sure that the operating environment is within the specified conditions at installa-
tion and remains within the specified conditions during the life of the system.
5
Application Precautions
Observe the following precautions when using the PC System.
WARNING
Always heed these precautions. Failure to abide by the following precautions
could lead to serious or possibly fatal injury.
Always turn OFF the power supply to the PC before attempting any of the fol-
lowing. Not turning OFF the power supply may result in malfunction or electric
shock.