Programming Console Operations
86
5. Press the MONTR Key to clear the specified regions of memory.
MONTR
00000MEMORY CLR
END HR       DM
6-2-3 Reading/Clearing Error Messages
This operation is used to display and clear error messages. It is possible to dis-
play and clear non-fatal errors and MESSAGE instruction messages in any
mode, but fatal errors can be cleared in PROGRAM mode only.
RUN
MONITOR
PROGRAM
OK
OK
OK
Before inputting a new program, any error messages recorded in memory
should be cleared. It is assumed here that the causes of any of the errors for
which error messages appear have already been taken care of. If the buzzer
sounds when an attempt is made to clear an error message, eliminate the
cause of the error, and then clear the error message. (Refer to Section 7 Test
Runs and Error Processing
 for troubleshooting information.)
Key Sequence
Follow the procedure below to display and clear messages.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Press the FUN and then the MONTR Key to begin the operation. If there are
no messages, the following display will appear:
FUN
MONTR
ERR/MSG CHK OK
If there are messages, the most serious message will be displayed when the
MONTR Key is pressed. Pressing MONTR again will clear the present mes-
sage and display the next most serious error message. Continue pressing
MONTR until all messages have been cleared. These are some examples
of error messages:
A memory error:
MONTR
MEMORY ERR
A system error:
MONTR
SYS FAIL FAL01
A message (displayed with MSG(46)):
MONTR
MATERIAL USED UP
All messages cleared:
MONTR
ERR/MSG CHK OK
6-2-4 Buzzer Operation
This operation is used to turn on and off the buzzer that sounds when Program-
ming Console keys are pressed. This buzzer will also sound whenever an error
occurs during PC operation. Buzzer operation for errors is not affected by this
setting.
This operation is possible in any mode.