6. TROUBLESHOOTING
6 - 1
6. TROUBLESHOOTING
POINT
Alarms and warnings are basically the same as those of MR-J3- B servo
amplifier. This chapter describes the contents different from those of MR-J3- B
servo amplifier.
As soon as an alarm occurs, make the servo-off status and interrupt the main
circuit power.
amplifier. This chapter describes the contents different from those of MR-J3- B
servo amplifier.
As soon as an alarm occurs, make the servo-off status and interrupt the main
circuit power.
If an alarm has occurred, refer to this chapter and remove its cause.
6.1 Alarms and warning list
When a fault occurs during operation, the corresponding alarm or warning is displayed. Refer to section 6.2 of
this manual and section 8.2 of the MR-J3- B Servo Amplifier Instruction Manual at an alarm occurrence and
section 6.3 of this manual and section 8.3 of the MR-J3- B Servo Amplifier Instruction Manual at a warning
occurrence, and then take the appropriate action. When an alarm occurs, the ALM turns off.
After its cause has been removed, the alarm can be deactivated in any of the methods marked
this manual and section 8.2 of the MR-J3- B Servo Amplifier Instruction Manual at an alarm occurrence and
section 6.3 of this manual and section 8.3 of the MR-J3- B Servo Amplifier Instruction Manual at a warning
occurrence, and then take the appropriate action. When an alarm occurs, the ALM turns off.
After its cause has been removed, the alarm can be deactivated in any of the methods marked
in the alarm
deactivation column. The alarm is automatically canceled after removing the cause of occurrence.
Alarm deactivation
Display
Name
92
Battery cable disconnection warning
Display Name Power
off on
Error
reset
reset
CPU
reset
reset
96
Home position setting error
10 Undervoltage
9F
Battery
warning
12
Memory error 1 (RAM)
E0
Excessive regeneration warning
13 Clock
error
E1
Overload warning 1
15
Memory error 2 (EEP-ROM)
E2
Direct drive motor overheat warning
16
Encoder error 1
E3
Absolute position counter warning
17 Board
error
E4
Parameter
warning
19
Memory error 3 (Flash-ROM)
E6
Servo forced stop warning
1A
Motor combination error
E7
Controller forced stop warning
1F
Encoder combination error
Cooling fan speed reduction
20
Encoder error 2
E8
warning
21
Encoder error 3
E9
Main circuit off warning
24
Main circuit error
EC
Overload warning 2
25
Absolute position erase
Warni
ngs
ED
Output watt excess warning
27
Initial magnetic pole detection error
2B
Encoder counter error
30
Regenerative error
(Note 1)
(Note 1)
(Note 1)
31 Overspeed
32 Overcurrent
33 Overvoltage
34
Receive error 1
(Note
2)
35
Command frequency alarm
36
Receive error 2
37 Parameter
error
42
Servo control error
(Note
3)
(Note 3)
45
Main circuit device overheat
(Note 1)
(Note 1)
(Note 1)
46
Direct drive motor overheat
(Note 1)
(Note 1)
(Note 1)
47
Cooling fan alarm
50
Overload 1
(Note 1)
(Note 1)
(Note 1)
51
Overload 2
(Note 1)
(Note 1)
(Note 1)
52 Error
excessive
8A
USB communication time-out error
8E
USB communication error
Ala
rms
888 Watchdog
Note 1. Deactivate the alarm about 30 minutes of cooling time after removing the cause of occurrence.
2. In some controller communication status, the alarm factor may not be removed.
3. Set parameter No.PS04 to "1
2. In some controller communication status, the alarm factor may not be removed.
3. Set parameter No.PS04 to "1
" to deactivate.