if the read/write address format is set to Rn, only Bit 0 ~ 23 are valid for Rn registers. 
(Notice: As the Jetter controller is a 24-bit format controller, the valid setting range is 24 Bits. 
If exceeds this range, HMI will stop read/write operation and show  “..Value is Incorrect” 
on the screen. So, please do not set any bit on Bit24 ~ Bit31 (Bit24 ~ Bit31 cannot be written).  
y
 
When using devices that the data length is in m Words,  
if the read/write address format is set to WRn, the Bit 0 ~ 15 of WRn register is the lowest word of a 
read/write value and the Bit 0 ~ 15 of WRn+m-1 register is the highest word of a read/write value. 
if the read/write address format is set to Rn, the Bit 0 ~ 23 of Rn register is the lowest word of a 
read/write value and the Bit 0 ~ 23 of Rn+1 register is the highest word of a read/write value. 
Each register is regards as a “Double Word”. The value of Bit24 ~ Bit31 is 0.  
Contacts 
Read/Write Range 
Contact type 
Format 
Word No. 
Bit No. 
Input Relay 
Inbb 
n: 1 ~ 32 
bb: 
01 ~ 08 
Output Relay 
Onbb 
n: 1 ~ 32 
bb: 
01 ~ 08 
Flag Relay 
Fn 
N/A 
n: 
0 ~ 32767 
C. Connections (Connector Pinouts) 
RS-232 
DOP Series 
9 pin D-SUB male (RS-232) 
Controller 
9 pin D-SUB male (RS-232) 
Controller 
9 pin D-SUB male 
(RS-232) 
RXD (2)
(2) TXD
TXD (3)
GND (5)
(3) RXD
(7) GND
 
 
 
 
 
 
 
Top View 
¾
  The pin definition of the cable of Jetter controller is different than the general RS-232 cable. Please pay 
close attention. 
 
Pin1