FieldServer IR-148 ユーザーズマニュアル

ページ / 19
FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual  
 
Page 10 of 19 
 
 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA  Web:www.fieldServer.com 
Tel: (408) 262-2299   Fax: (408) 262-9042   Toll_Free: 888-509-1970   email: support@fieldServer.com 
5. 
Configuring the FieldServer as a Honeywell Zellweger IR-148 Server 
For  a  detailed  discussion  on  FieldServer  configuration,  please  refer  to  the  FieldServer 
Configuration Manual.  The information that follows describes how to expand upon the factory 
defaults provided in the configuration files included with the FieldServer (See “.csv” sample files 
provided with the FieldServer). 
This section documents and describes the parameters necessary for configuring the FieldServer 
to report sensor data to Honeywell Zellweger IR-148 Client.  As a Server this driver sends Gas 
value, Alarm, Trouble and Lock point messages.  The driver can be locked to send data for only 
one particular sensor.
 
The configuration file tells the FieldServer about its interfaces, and the routing of data required. 
In  order to  enable the  FieldServer for  Honeywell  Zellweger IR-148  communications,  the  driver 
independent  FieldServer  buffers  need  to  be  declared  in  the  “Data  Arrays”  section,  the 
FieldServer  virtual  node(s)  needs  to  be  declared  in  the  “Server  Side  Nodes”  section,  and  the 
data  to  be  provided  to  the  Clients  needs  to  be  mapped  in  the  “Server  Side  Map  Descriptors” 
section.  Details on how to do this can be found below. 
Note  that  in  the  tables,  *  indicates  an  optional  parameter,  with  the  bold  legal  value  being  the 
default. 
5.1. 
Server Side Connection Descriptors 
Section Title 
Connections 
Column Title 
Function 
Legal Values 
Port 
Specify  which  port  the  device  is 
connected to the FieldServer 
P1-P8 
(with 
232/485 
converter), R1-R2
2
 
Protocol 
Specify protocol used 
InfraTox or Infra-Tox 
Baud* 
Specify baud rate 
110  –  115200,  standard 
baud rates only 
9600 
Parity* 
Specify parity 
Even,  Odd,  None,  Mark, 
Space 
Data_Bits* 
Specify data bits 
7, 8 
Stop_Bits* 
Specify stop bits 
Handshaking* 
Specify hardware handshaking 
RTS, RTS/CTS, None 
 
Example 
 
//    Server Side Connections 
 
Connections 
Port, 
Protocol, 
Baud, 
Parity, 
Data_Bits 
R1, 
InfraTox, 
19200, 
None, 
 8 
 
                                                 
2
 
Not  all  ports  shown  are  necessarily  supported  by  the  hardware.  Consult  the  appropriate  Instruction 
manual for details of the ports available on specific hardware.