FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual  
 
Page 12 of 19 
 
 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA  Web:www.fieldServer.com 
Tel: (408) 262-2299   Fax: (408) 262-9042   Toll_Free: 888-509-1970   email: support@fieldServer.com 
5.3.2. 
Driver Specific Map Descriptor Parameters 
Column Title 
Function 
Legal Values 
Node_Name 
Name  of  Node  to  which  data 
has to be sent. 
One  of  the  node  names 
specified  in  “Server  Node 
Descriptor” - section 5.2 
Length 
Length of Map Descriptor 
1-Maximum  of  Data  Array 
length.  
Da_Byte_Array_Name* 
Name  of  Data  Array  used  to 
lock  the  sensor.    Driver  will 
report  data  for  the  locked 
sensor only. 
One  of  the  Data  Array 
names  from  “Data  Array” 
section above 
Data_Byte_Offset* 
Specifies 
offset 
for 
Da_Byte_Array_Name  
Data  array.    This  memory 
location  will  be  checked  every 
time  if  the  user  has  locked  a 
sensor. 
If 
this 
parameter 
is 
not 
specified, the driver will use the 
Data_Array_Offset value.   
1-Maximum  of  Data  Array 
length.  
Infra_Func 
For  quality  assurance  this 
parameter  is  used  to  send  a 
message  to  a  Client  from  a 
Map_Descriptor_Name*.ini file. 
With  the  use  of  this  function 
Data_Array_Offset value will be 
used as line number from INI to 
send. 
INFRA_SIMULATION: 
only 
numbered  line  will  be  sent  to 
Client by the Map Descriptor. 
INFRA_SIMULATION_ALL: 
 
Starting at the numbered line all 
lines will be sent one by one to 
the  Client  until  the  end  of  the 
file is reached. 
INFRA_SIM_ALL_REPEAT: 
  
Repeatedly 
Starting 
from 
numbered line to end of the file 
all  lines  will  be  sent  to  Client 
one  by  one  by  this  single  Map 
Descriptor. 
Note: Ini must show all bytes as 
two 
character 
hex 
representation  and  first  line  of 
should be 
// FILE_IN_HEX_FORMAT
 
INFRA_SIMULATION 
INFRA_SIMULATION_ALL 
INFRA_SIM_ALL_REPEAT