OBSERVED PROBLEM
Pilot burning, no gas to burner, 
valve  knob  "ON",  wall  switch 
"ON"
Frequent  pilot/burner  outage 
problem
REMEDY
1. Check wall switch and wires 
for proper connections. Jump-
er wire across terminals at wall 
switch.  If  burner  comes  on, 
replace defective wall switch. 
If okay, jumper wires across 
wall switch wires at valve. If 
burner  comes  on,  wires  are 
faulty or connections are bad
2. Check  thermopile  with  mil-
livolt meter. Take reading at 
thermopile  terminals  of  gas 
valve. It should read 325 mil-
livolts minimum with optional 
wall switch "OFF". Replace 
faulty thermopile if reading is 
below specified minimum.
3. Check burner orifice for stop-
page and remove
1. Clean and/or adjust pilot flame 
for maximum flame impinge-
ment  on  thermocouple  (see 
Figure 13, page 11)
POSSIBLE CAUSE
1. Wall  switch  or  wires 
defective
2. Thermopile  may  not  be 
generating  sufficient  mil-
livoltage.
3. Plugged burner orifice
 
1. Pilot flame may be too low 
or  blowing  (high)  causing 
the pilot/valve safety to drop 
out
TROUBLESHOOTING
Continued