Thermo Products CBD1-50N ユーザーズマニュアル

ページ / 57
All installations and services must be performed by qualified service personnel. 
 
 
 
 
CDB1 SERIES 
 
MODEL NO. 
CDB1-50 
CDB1-75 
CDB1-100 
CDB1-125 
BTU/HR INPUT 
50,000 
75,000 
100,000 
125,000 
BTU/HR OUTPUT 
47,000 
70,000 
94,000 
116,000 
 
 
 
 
 
HT. OF CASING 
46-1/4” 
46-1/4” 
46-1/4” 
46-1/4” 
WIDTH OF CASING 
17” 
17” 
21” 
24” 
DEPTH OF CASING 
27-1/2” 
27-1/2” 
27-1/2” 
27-1/2” 
WARM AIR OUTLET 
15 x 18 
15 x 18 
19 x 18 
22 x 18 
RETURN AIR INLET 
15 x 22 
15 x 22 
19 x 22 
22 x 22 
 
 
 
 
 
DIA. OF FLUE 
2” 
2” 
3” 
3” 
DIA. OF COMBUSTION 
AIR INTAKE 
2” 
2” 
3” 
3” 
 
 
 
 
 
CFM @ .2” & .5” w.c.  
EXTERNAL STATIC PRESSURE 
.2”   .5” 
.2”   .5” 
.2”   .5” 
.2”   .5” 
 
 
 
 
 
@HI SPEED 
1120   930 
1530   1340 
1830   1590 
2280   2010 
@MH SPEED 
1000   750 
1270   1110 
1660   1460 
1830   1650 
@ML SPEED 
--         -- 
1050   930 
1520   1340 
1750   1570 
@LO SPEED 
616    420 
850    720 
1370   1230 
1660   1530 
 
 
 
 
 
TEMPERATURE RISE 
70 
70 
70 
70 
BLOWER MOTOR HP 
.20 
.41 
.50 
.75 
NO. OF SPEEDS 
RUN CAPACITOR 
10 mfd 
10 mfd 
10 mfd 
15 mfd 
LARGEST RECOMMEDED 
AIR CONDITIONER 
2 Ton 
3.5 Ton 
4 Ton 
5 Ton 
SIZE OF FILTERS 
21-3/4” x 14”(2) 
21-3/4” x 14”(2) 
21-3/4” x 14”(2) 
21-3/4” x 14”(2) 
NOTES: 
1.  BTU output based on annual fuel utilization efficiency rated by manufacturer. 
2.  On all outlet and inlet dimensions, the first dimension is width. 
3.  To permit largest recommended air conditioning (at .5 static pressure), selection of the highest motor speed is 
required. 
4.  Electrical characteristics at 115 volts, 60 Hz., 1 phase (less than 15 amps. for all models). 
5.  All specifications are subject to change without notice.