Honeywell Ademco Vista Series Commercial Burglary Partitioned Security System With Scheduling ユーザーズマニュアル
– 5 –
VISTA-50P/VISTA-50PUL Programming Form
Some fields are programmed for each partition (shown as shaded fields). If you are programming a multiple-partition system,
see the Partition-Specific Fields section for programming these fields. Standard default (*97) values are shown in brackets [ ].
see the Partition-Specific Fields section for programming these fields. Standard default (*97) values are shown in brackets [ ].
*00
INSTALLER CODE
| | |
Enter 4 digits, 0-9 [4140]
*02 *05
RESPONSE TYPES FOR ZONES
Skip these fields. Use #93 Menu Mode, Zone
Programming to program the response types.
Programming to program the response types.
*09
ENTRY DELAY #1
[02]
|
00, 02-15 times 15 seconds
Maximum "03" for UL.
*10
EXIT DELAY #1
[03]
|
00, 03-15 times 15 seconds
Maximum "04" for UL installations.
*11
ENTRY DELAY #2
[06]
|
00, 02-15 times 15 seconds (must be longer than Entry Delay
#1). Maximum "03" for UL installations.
#1). Maximum "03" for UL installations.
*12
EXIT DELAY #2
[08]
|
00, 03-15 times 15 seconds (must be longer than Exit Delay
#1). Maximum "04" for UL installations.
*13
ALARM SOUNDER DURATION
[04]
|
01-15 times 2 minutes. Must be minimum 16 minutes for UL
installations.
installations.
*14
ZONE 9 RESPONSE TIME
[0]
Enter 1 for fast response time 10ms
Enter 0 for normal response time 350ms.
Must be 0 for UL installations.
*15
KEYSWITCH ASSIGNMENT
[0]
Enter partition in which keyswitch used,
1-8;
0=disable
*16
CONFIRMATION OF ARMING DING
[0]
1=enable; 0=disable.
Must be "1" for UL Installations.
*17
AC LOSS KEYPAD SOUNDING
[0]
1=yes;
0=no
*19
RANDOMIZE AC LOSS REPORT
[0]
1=10-40 min; 0=normal report (about 2 min. after AC loss).
*20
VIP MODULE PHONE CODE
| |
Enter 01 - 09 for the first digit; enter
[00],
[11]
11 for “*” or 12 for “#” for the second digit.
Must be set to "0" for UL installations.
*21
PREVENT FIRE TIMEOUT
[0]
1=No timeout; 0=Timeout.
*22
KEYPAD PANIC ENABLES
[001]
1=enable; 0=disable
995 996 999
*23
MULTIPLE ALARMS
[1]
1=yes; 0=no
*24
IGNORE EXPANSION ZONE TAMPER
[0]
1=Ignore; 0=Enable tamper for RF and RPMs.
Must be "0" for UL installations if using these devices.
*25
BURG.TRIGGER FOR RESPONSE TYPE 8 [1]
1=enable;
0=disable
*26
INTELLIGENT TEST REPORTING
[0]
1=yes (no report sent if any other report was recently sent);
0=no (send report at programmed interval, field *27)
0=no (send report at programmed interval, field *27)
Must be 0 for UL installations.
*27
TEST REPORT INTERVAL
[024
] | | |
Enter interval in hours, 001-999; 0000=no report;
Max. 024 for UL installations.
*28
POWER UP IN PREVIOUS STATE
[1]
1=yes; 0=no; "1" for UL installations.
*29
QUICK ARM
[1]
1=yes;
0=no
*30
TOUCHTONE OR ROTARY DIAL
[0]
1=TouchTone; 0=rotary
*31
PABX ACCESS CODE
| | | |
00-09; B-F (11-15)
*32
PRIM. SUBS. ACCT #
| | | |
Enter 00-09; B-F (11-15) [15 15 15 15]
*33
PRIMARY PHONE NUMBER
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause
*34
SECONDARY PHONE NUMBER
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause
*35
DOWNLOAD PHONE NO.
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause
*36
DOWNLOAD ID NO.
| | | | | | | |
Enter 00-09; A-F (10-15) [15 15 15 15 15 15 15 15]
*37
DOWNLOAD COMMAND ENABLES
Dlr Shtdwn
Sys Shtdwn
0
Not Used
Rmt Byp
Rmt Disarm
Rmt Arm
Upld Pgm
Dwnld Pgm
See field 1*53 for Callback disable option; [1=enable];
0=disable. For UL installations, all entries must be "0."
0=disable. For UL installations, all entries must be "0."
*38
PREVENT ZONE XX BYPASS
[00]
|
01-86; 00 if all zones (except fire zones) can be bypassed