Mitsubishi Electronics QD75MH1 ユーザーズマニュアル

ページ / 838
 
 
 
9 - 66 
MELSEC-Q
 
9   MAJOR POSITIONING CONTROL 
 
In circular interpolation control with center point designation, an angular velocity is 
calculated on the assumption that operation is carried out at a command speed on 
the arc using the radius calculated from the start point address and center point 
address, and the radius is compensated in proportion to the angular velocity 
deviated from that at the start point. 
Thus, when there is a difference (error) between a radius calculated from the start 
point address and center point address (start point radius) and a radius calculated 
from the end point address and center point address (end point radius), the 
composite speed differs from the command speed as follows. 
 
 Start point radius > End point radius: As compared with the speed without error, 
the speed becomes slower as end point 
address is reached. 
 Start point radius < End point radius: As compared with the speed without error, 
the speed becomes faster as end point 
address is reached. 
 
 Restrictions 
 
(1)  2-axis circular interpolation control cannot be set in the following cases. 
 
 When "degree" is set in "
Pr.1
 Unit setting" 
 When the units set in "
Pr.1
 Unit setting" are different for the reference axis 
and interpolation axis. ("mm" and "inch" combinations are possible.) 
 When "reference axis speed" is set in "
Pr.20
 Interpolation speed 
designation method" 
 
(2)  An error will occur and the positioning start will not be possible in the following 
cases. The machine will immediately stop if the error is detected during 
positioning control.  
 
 When the radius exceeds "536870912 (=2
29
)". (The maximum radius for 
which circular interpolation control is possible is "536870912 (=2
29
)" 
...  An "Outside radius range error (error code: 544)" will occur at positioning 
start. 
 When the start point address is the same as the center point address 
...  A "Center point setting error" (error code: 527) will occur. 
 When the end point address is the same as the center point address 
...  A "Center point setting error" (error code: 527) will occur. 
 When the center point address is outside the range of -2
31
 to 2
31
-1 