Simple Applications 
International English 
22 
MICROMASTER  Applications Handbook 
7
6
5
8
MICROMASTER
DIN 1
+24 V Output
DIN 2
DIN 3
Digital
Inputs
 
Figure 5-2 
Using all the Digital Inputs 
5.3 
Selecting and Using the Fixed Frequencies 
The digital inputs can be used to select fixed frequencies.  Set parameter P1000 to 
3 (select fixed frequency operation), and set parameters P0701, 2,and 3 to 16.  
These switches can now be used to select fixed frequencies 1, 2 and 3 (default 
values 0, 5 and 10 Hz).  By setting P0701 etc. to 16, a ‘RUN’ signal is automatically 
generated when a fixed frequency is selected. 
Closing more than one switch will simply add the two fixed frequencies together. 
Other fixed frequencies (including reverse – negative – values) can be selected by 
changing the value of parameters P1001, 2, 3 etc.  
5.3.1 
More Complex Uses of Fixed frequencies 
If the corresponding digital inputs are reprogrammed from 16 to 17, the inputs will 
selected fixed frequencies in binary coding, allowing the three inputs to select up to 
8 digital inputs.  However, a separate ‘ON’ command will be required 
The fixed frequencies can be added or scaled to the fixed frequencies by changing 
parameter P1000 and P1071. 
Please consult the Parameter List for additional details. 
5.4 
Using other digital input features 
All the digital inputs have many different functions, which can be programmed by 
setting parameters P0701-3,  The analog input can even be programmed as a 
digital input using parameter P0704.  Simple uses include: 
001 Run 
right 
002 Run 
left 
012 Reverse 
010 Jog 
right. 
Other settings that may prove useful: 
016  Select fixed frequency + on (see above) 
012 Fault 
reset 
029 External 
trip.