Mitsubishi Electronics Q68ADI ユーザーズマニュアル

ページ / 140
6 - 3                                                                                                                                                       6 - 3
MELSEC-Q
6   PROGRAMMING
6.1.2 Programming example
Digital output value read processing
0
MOV
D11
D101
CH1 Digital 
output
X10
26
Error 
reset 
signal
X0F
Error  
flag
52
END
Transfer digital output values D11 
to D13 read using automatic 
refresh to D101 to D103 after A/D 
conversion is completed.
X11
X0
X0E
Module 
READY
A/D 
conversion 
completed 
flag
Read 
digital 
values
MOV
D12
D102
CH2 Digital 
output
MOV
D13
D103
CH3 Digital 
output
Error code display and reset processing
BCD
D14
K3Y20
Error code
SET
Y0F
Error clear
request
Y0F
49
Error 
reset 
request
X0F
Error  
flag
RST
Y0F
Error clear
request
Clear the error code.
Output the error code to Y20 to 
Y2B by BCD code.