Mitsubishi Electronics Q68ADI ユーザーズマニュアル

ページ / 140
6 - 4                                                                                                                                                       6 - 4
MELSEC-Q
6   PROGRAMMING
6.2 Programming Example without Using the Utility Package
(1)   Programming example using the FROM/TO commands
Set the A/D conversion enabled channel (initial setting)
0
X10
139
Error 
reset 
signal
X0F
Error  
flag
170
END
Read digital output values for 
CH1 to 3
X0
Module 
READY
Error code display and reset processing
BCD
D14
K3Y20
Error code
SET
Y0F
Error clear
request
Y0F
167
Error 
clear
request
X0F
Error  
flag
RST
Y0F
Error clear
request
Output the error code to Y20 
to Y2B by BCD code.
T0
H0
K1
K0
H8
CH1 to CH3 are A/D conversion 
enabled
T0
H0
K1
K2
K50
Set the average number of times 
for CH2 to 50 times
T0
H0
K1
K3
K1000
Set the average time for CH3 to 
1000 ms
T0
H0
K1
K9
H604
Specify averaging processing
Y9
SET
Operating 
condition 
setting request
Y9
101
Operating 
condition 
setting 
request
X9
Operating 
condition 
setting completed
RST
Y9
Operating 
condition 
setting request
X11
104
Read 
digital 
values
X0
Module 
READY
CH1 
Digital 
output
Digital output value read processing
X0E
A/D 
conversion 
completed 
flag
FROM
H0
K1
K11
D11
CH2 
Digital 
output
FROM
H0
K1
K12
D12
CH3
Digital 
output
FROM
H0
K1
K13
D13
Error code
FROM
H0
K1
K19
D14
Set Y9 (operating condition 
setting request) from ON to OFF 
and enable the initial setting
Clear the error code.