Running the setpoint
ramp
ramp
Running a Setpoint Ramp includes starting, holding, viewing the ramp
time, ending the ramp, and disabling it.
time, ending the ramp, and disabling it.
Procedure
Table 5-15 lists the procedure for running the Setpoint Ramp.
Table 5-15
Procedure for Running a Setpoint Ramp
Step
Operation
Press
Action
1
Put the controller
into Automatic
mode
into Automatic
mode
MANUAL
AUTO
until “A” indicator is ON and you will see:
Lower Display
Upper Display
H and the PV value
SP and the present
setpoint value
setpoint value
2
Set Start
Setpoint
Setpoint
or
until the start setpoint value you desire is
indicated in the lower display:
indicated in the lower display:
Lower Display
Upper Display
H and the PV value
SP and the start
setpoint value
setpoint value
3
Start the Ramp
RUN
HOLD
You will see:
Lower Display
Upper Display
R and the PV value
SP and a changing
setpoint value
setpoint value
ATTENTION
The value in the lower
display will be increasing or decreasing
toward the final setpoint value. The PV value
in the upper display will also change.
toward the final setpoint value. The PV value
in the upper display will also change.
4
Hold/Run the
Ramp
Ramp
RUN
HOLD
This holds the ramp at the current setpoint
value.
value.
Press again to continue run.
5
View the
remaining ramp
time
remaining ramp
time
LOWER
DISPLAY
until you see:
Lower Display
Upper Display
R or H and
the PV value
the PV value
RAMP XXXM
(Time remaining)
(Time remaining)