UDC 3300 Controller Product Manual
167
Step
Operation
Press
Action
6
Change setpoint
during Hold
mode
 or
to change the “HELD” setpoint if the ramp is
on “HOLD.”
However, the ramp time remaining is not
changed. Therefore, when returning to RUN
mode, the setpoint will ramp at the same rate
as prior to local setpoint changes and will
stop if the final setpoint is reached before
time expires.
If the time expires before the final setpoint is
reached, it will jump to the final setpoint.
7
End the Ramp
When the final setpoint is reached, the
“R” changes to “H” in the upper display and
the controller operates at the new setpoint.
ATTENTION
 Any time the local setpoint
is different from the final setpoint value and
the RUN/HOLD   key is pressed, the ramp
will start again.
8
Disable the
setpoint ramp
function
SET UP
until you see:
SP RAMP
Lower Display
SET UP
Upper Display
FUNCTION 
LOOP 1/2
You will see:
SP RAMP
Lower Display
Upper Display
DISABL
—Disables SP Ramp
 
ENABLE
—Enables SP Ramp for Loop 1
 
ENABL2
—Enables SP Ramp for Loop 2
 
ENAB12
—Enables Sp Ramp for  
Loops 1 and 2
until you see:
SP RAMP
Lower Display
DISABL
Upper Display
9
Return to normal
operating mode
LOWER 
DISPLAY