Honeywell UDC 3300 사용자 설명서
4/00
UDC 3300 Controller Product Manual
189
Table 5-32
Digital Inputs 1 and 2 Combination
DIG IN1
DIG COMB
Action
Example
NONE
Any Selection
No action will occur when the digital
input is active.
input is active.
ENABLED
DISABLED
The DIG IN condition will occur
when the Digital Input is active.
when the Digital Input is active.
DIG IN1 = TO MAN
DIG1 COM = DISABL
DIG1 COM = DISABL
Loop 1 will switch to MANUAL
when digital input 1 is active.
when digital input 1 is active.
ACTION
DISABLED
DISABLED
ENABLED
No action will occur when the digital
input is active.
input is active.
DIG IN1 = ToPID2
PID SETS = 1 ONLY
DIG1 COM = +ToSP2
LSP’S = TWO
PID SETS = 1 ONLY
DIG1 COM = +ToSP2
LSP’S = TWO
DIG IN1 is action disabled
because PID SETS is set to
1 ONLY. Therefore, when digital
input 1 is active, no action will
occur even though DIG1 COM is
enabled.
because PID SETS is set to
1 ONLY. Therefore, when digital
input 1 is active, no action will
occur even though DIG1 COM is
enabled.
ENABLED
ACTION
DISABLED
DISABLED
Action is indeterminate when the
digital input is active.
digital input is active.
DIG IN1 = ToPID2
PID SETS = 2KEYBD
DIG1 COM = +ToSP2
LSP’S =1 ONLY
PID SETS = 2KEYBD
DIG1 COM = +ToSP2
LSP’S =1 ONLY
Because DIG1 COM is action
disabled, the action will be
indeterminate when DIG IN1 is
active.
disabled, the action will be
indeterminate when DIG IN1 is
active.
ENABLED
ENABLED
Both DIG IN and DIG COM action
will occur.
will occur.