UDC 3300 Controller Product Manual
4/00
5.19 Auto/Manual Station
Introduction
When you select “AM STA” (auto manual station) under the Option Set
Up group function prompt “DIG IN1” or “DIG IN2” (digital input option),
contact closure on the selected digital input causes the controller to switch
to Auto/Manual Station mode.
Function
As shown in Figure 5-5, State 2 is the “A/M Station mode” where the
programmable logic controller (PLC) output is sent through the
Auto/Manual Station. You can switch to manual and change the output at
the controller. (It uses PID set 2.)
State 1 is the “Backup PID mode” which is triggered by opening the
digital input. (It uses PID set 1.)