UDC 3300 Process Controller Product Manual
231
7.6  Restoring Factory Calibration
How to restore it
The factory calibration constants for all the input actuation types that can
be used with the controller are stored in its nonvolatile memory. Thus,
you can quickly restore the “Factory Calibration” for a given input
actuation type by simply changing the actuation type to another type and
then changing it back to the original type. See Table 7-6 for the procedure.
Procedure
Table 7-6 lists the procedure for restoring factory calibration.
Table 7-6
Restoring Factory Calibration
Step
Operation
Press
Action/Result
1
Set LOCKOUT
to CALIB or
NONE
SET 
 UP
until you see:
Upper Display
Lower Display
SET UP
TUNING
FUNCTION 
LOOP 1/2
until you see:
Upper Display
Lower Display
LOCKOUT
One of the following 
NONE 
CALIB 
+CONF 
+VIEW 
MAX
 or 
Until CALIB or NONE is in the upper display.
2
Enter
INPUT 1 or 2
Setup Group
SET 
 UP
until you see:
Upper Display
Lower Display
SET UP
INPUTn
n = 1, 2, or 3
FUNCTION 
LOOP 1/2
until you see:
Upper Display
Lower Display
IN nTYPE
Current Selection
n = 1, 2, or 3
 or 
to change the current selection to another
selection.