UDC 3300 Controller Product Manual
233
Section 8 – Output Calibration
8.1 Overview
Introduction
This section describes the field calibration procedures for the following
types of outputs:
• Current Output
• Position Proportional and 3 Position Step Output
• Auxiliary Output
What’s in this section
This section contains the following topics:
Topic
See Page
8.1
Overview
233
8.2
Current Proportional Output Calibration
• Introduction
• Equipment Needed
• How to Connect the Calibrator
• Calibration Procedure
234
234
234
234
235
8.3
Position Proportional and Three Position Step Output
 Calibration
• Position Proportional Control
• 3 Position Step Control
• Equipment Needed
• What connection to make
• Calibration Procedure
236
236
236
236
236
237
8.4
Auxiliary Output Calibration
• Introduction
• Equipment Needed
• How to Connect the Calibrator
• Calibration Procedure
240
240
240
240
241
  WARNING—SHOCK HAZARD   !
OUTPUT CALIBRATION MAY REQUIRE ACCESS TO
HAZARDOUS LIVE CIRCUITS, AND SHOULD ONLY BE
PERFORMED BY QUALIFIED SERVICE PERSONNEL.
MORE THAN ONE SWITCH MAY BE REQUIRED TO DE-
ENERGIZE UNIT BEFORE CALIBRATION.