UDC 3300 Controller Product Manual
235
Procedure
The procedure for calibrating the Current Proportional Output is listed in
Table 8-2. Make sure LOCKOUT in the Tuning Set Up group is set to
NONE. See Section 3 – Configuration.
Table 8-2
Current Proportional Output Calibration Procedure
Step
Description
Press
Action
1
Enter Calibration Mode
SET UP
until you see
CURRENT
Lower Display
CALIB
Upper Display
2
Calibrate 0 %
FUNCTION 
LOOP 1/2
You will see:
Lower Display
Upper Display
ZERO VAL
a value between 1 and 2048
 or 
until the desired 0 % output is read on the milliammeter.
Use the values shown below depending on the action of
your valve.
0 mA
For 0 to 20 mA Direct Action*
20 mA
For 0 to 20 mA Reverse Action
4 mA
For 4 to 20 mA Direct Action
20 mA
For 4 to 20 mA Reverse Action
3
Calibrate 100 %
FUNCTION 
LOOP 1/2
This stores the 0 % value and you will see:
Lower Display
Upper Display
SPAN VAL
a value between 1 and 2048
 or 
until the desired 100 % output is read on the milliammeter.
Use the values shown below depending on the action of
your valve.
20 mA
For 0 to 20 mA Direct Action
0 mA
For 0 to 20 mA Reverse Action*
20 mA
For 4 to 20 mA Direct Action
4 mA
For 4 to 20 mA Reverse Action
4
Exit the Calibration Mode
FUNCTION 
LOOP 1/2
The controller will store the span value.
LOWER 
DISPLAY
or
SET UP
To exit the calibration mode.
*When attempting to achieve 0 mA, always adjust the output to about 0.5 mA, and slowly decrease until the
output just goes to zero. Further decrementing will not change the output current (since the circuit cannot
produce negative current) but will affect the accuracy of the output by creating a dead zone where no
current flows.