UDC 3300 Process Controller Product Manual
4/00
3.16 
Loop 2 Control Parameters Set Up Group
Introduction
The functions listed in this group define how Loop 2 of a Two Loop
process controller will control the process.
Only available on Expanded Controller Model DC330E-XX-XXX.
Function prompts
Table 3-13 lists all the function prompts in the Control 2 Set Up group.
Table 3-13
Control 2 Group Function Prompts
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
Refer
to
PV 2 SRC
Process Variable Source
INP 1
INP 2
IN AL1
IN AL2
INP 3
INP 2
Section
4.12
FORCE MA
Force Manual
DISABL
LINK12
DISABL
PID SETS
Tuning Parameter Sets
1 ONLY
2KEYBD
2PV SW
2SP SW
GAIN S (Gain scheduling
automatically disables Accutune for
this loop)
1 ONLY
SW VALUE
Automatic Switchover Value
Value in engineering units within PV
or SP range limits
0.00
LSP’S
Local Setpoint Source
1 ONLY
TWO
THREE (Selection automatically
disables RSP SRC)
1 ONLY
RSP SRC
Remote Setpoint Source
NONE
INP 2
IN AL1
IN AL2
INP 3
NONE
AUTOBIAS
Automatic Bias
ENABLE
DISABL
DISABL
SPTRACK
Local Setpoint Tracking
NONE
PV
RSP
NONE
SP HiLIM
Setpoint High Limit
0 to 100 % of PV span input in
engineering units
1000
SP LoLIM
Setpoint Low Limit
0 to 100 % of PV span input in
engineering units
0
ACTION
Control Output Direction
DIRECT
REVRSE
REVRSE