UDC 3300 Process Controller Product Manual
61
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
Refer
to
OUT RATE
Output Change Rate
ENABLE
DISABL
DISABL
Section
4.12
PCT/M UP
Output Rate Up Value
0 to 9999 % per minute
0
PCT/M DN
Output Rate Down Value
0 to 9999 % per minute
0
OUTHiLIM
High Output Limit
–5 to 105 % of output
100
OUTLoLIM
Low Output Limit
–5 to 105 % of output
0
I HiLIM
High Reset Limit
Within the range of the output limits
100.0
I LoLIM
Low Reset Limit
Within the range of the output limits
0.0
DROPOFF
Controller Dropoff Value
–5 to 105 % of output
0
DEADBAND
Output Relay Deadband
–5.0 to 5.0 %
1.0
FAILMODE
Failsafe Mode
NO LAT
LATCH
NO LAT
FAILSAFE
Failsafe Output Value
Set within the range of the output
limits. 0 to 100 %
0