EXCEL 10 W7761A INPUT/OUTPUT DEVICE
40
74-2699
This procedure will use switching logic to add the pseudo analog point. With the RIO plant having the focus, go into
switching logic. Select the 
Software Points
 menu item and then 
Pseudo Analog
. The 
Create/Select Software Point
 <
Va
>
dialog box will be displayed. Type in a New point name for the enthalpy sensor (such as 
OaEnthaply
) and click on the 
OK
button. The new point that was just created will be added to the screen as the header point for switching logic table and
also added to the 
Point List
 . Select the 
Cancel
 button to exit the 
Create/Select Software Point
 <
Va
> dialog box. Exit
switching logic by selecting the 
File
 menu item and 
Exit
. CARE will display the 
Delete Unused Software Points
 list box.
Click the 
Cancel
 button to continue.
2. Go into the 
Data Point Editor
 (
Controller/Edit/Data Point Editor
) and under 
Point
 select the pseudo analog point that was
just created and click the 
OK
 button. Select the drop down list for the 
Engineering Unit
 and scroll through the list until the
mA (mA matches the engineering unit of the RIO input) engineering units are displayed. Select the mA engineering unit
that is shown with one decimal place (number 66) and click the 
OK
 button to save the selection. Cancel the 
User
Address
 list box and select 
File/Exit
 to exit out of the Data Point Editor.
3. Translate the Zone Manager and Export the Zone Manager files to E-Vision by selecting the 
Project
 and 
Export to E-
Vision
 menu items. Type in the name of the Zone Manager Export file when the 
Export Zone Manager
 dialog box is
displayed. Select the project and the Zone manager within that project that is being exported and click the 
Export
 button.
Exit CARE and Start E-Vision. Select the E-Vision project to open and the CARE Export Filename created above. Once
the project is open, select the RIO device that the enthalpy sensor is connected to and go into the 
Application Selection
screen (offline) by selecting the 
Controller
, then the 
Application Selection
 menu items. From the 
Inputs
 tab of the
Application Selection
 dialog box, add Oa_Enthalpy to either analog input 5 or 6 and select the 
OK
 button to save the
selection.
4. Select the 
Controller
 menu item and then 
Import
 from CARE to import the Zone Manager files with the new pseudo
analog point. If this function has already been performed before, the user will be prompted with the message CARE
Export File has already been imported, do you want to import again?. Select 
Yes
 to continue with the Import. When the
import is finished, E-Vision displays the message CARE Export File has been imported. Select 
OK
 to continue.
5. Select the 
Network
 menu item and then 
Map C-Bus Points
. Select 
RIO1
 as the Controller Type from the 
Map C-Bus
Points
 dialog box. Under 
Unmapped CARE
, select the name of the RIO device that the enthalpy sensor was added to in
CARE. Under 
Unmapped Excel 10
, select the name of the RIO device that the actual enthalpy sensor was added to
(both names should be the same). Next, select the 
Custom
 button and the 
Custom Mapping CARE Points
 dialog box will
be displayed. Select the 
OaEnthalpy
 point under 
CARE Points
 and 
CurrentAI
 under 
Excel 10
. CurrentAI is the user
address in the RIO device that contains the actual sensor value for the OaEnthalpy (C7400A1004, 4 to 20 mA device).
Select the 
Map
 button to add the OaEnthalpy point to the list of 
Mapped Points
. Click on the 
Close
 button to exit the
Custom Mapping CARE Points
 dialog box. Click on the 
Close
 button to exit the 
Map C-Bus Points
 dialog box.
6. To use the OaEnthalpy custom mapped point with other Excel 10 controllers on the E-Bus, select the 
Network
 menu item
and 
Refer Excel 10 Points
. Select the RIO device name as the 
Source Excel 10
 and then scroll down the list of 
Excel 10
Points
: until you reach 
CurrentAI
 and select it. Select an Excel 10 controller from the 
Destination Excel 10
 list. For
example if the user had selected a CVAHU controller from the 
Destination Excel 10
 list, the user would select from the
Excel 10 Points
 list as the destination point and then click on the 
Add
 button to add the point association (Binding)
between the RIO and CVAHU controllers. If 
DestOaEnth
 is already being used in an association, then the message 
At
Least
 one of the output network variables is in an existing connection and E-Vision will not allow this association to be
added. In order to add this association, the user has to remove any other associations with the 
DestOaEnth
 point. Select
the 
Close
 button to exit out of the 
Refer Excel 10 Points
 dialog box. Any controllers involved in the new association or
change in an existing association will require commissioning.
7. Select the 
Controller
 menu item and the 
Update Zone Manager Files
. E-Vision will add the custom mapping information
to the Zone Manager files. When the 
Update Zone Manager Files
 function is done, commission any controllers that need
to be commissioned, then close the E-Vision project and exit out of E-Vision.
8. Start CARE and open the Zone Manager that was just updated through the 
Update Zone Manager Files
 function and
start XI584 by selecting the 
Controller
Tools
 and 
XI584
 menu items. Once XI584 is started, select the 
Utilities
 and 
File
Transfer
 menu items and select 
CARE Import
. Select the project and the Zone Manager that was just updated and select
Import
 and click 
OK
 on the 
Select Target Controller
 dialog box. When the CARE Import is complete, close the 
CARE
Import
 dialog box. If this is the initial loading of the Zone Manager, then it will have to be reset and the CPU address set
by the XI581 Emulation function (
Applications
XI581 Emulation
 menu). Select the 
Utilities
File Transfer
 menu items and
select 
Download
. The 
Download
 dialog box will be displayed. Check the 
All
 selection and click the 
Controller
 button.
When the 
Select Controller/Subsystem
 dialog box is displayed, make sure that the correct CPU address or name is high
lighted and select the 
OK
 button. Click the 
Download
 button and click 
Yes
 to the message 
Replace
 updated application
part in controller (CPU address or Controller name). When the download is complete, exit out of the 
Download
 dialog
box. From the XI584 main menu, select the 
Data
Access by User Address
 menu items. Type 
OaEnthalpy
 in the 
Search
For User Address
 and click the 
Search
 button. When the 
OaEnthalpy
 point displays in the 
User Addresses
 list, click on
the point and select the 
Attributes
 button. XI584 will now display the value of the enthalpy sensor connected to the RIO
device. This point can now be used in the Zone Manager control strategy or switching logic. This point can be used in
other Excel 5000 (C-Bus) controllers by assigning a global analog point in the destination controller with the user address
name of 
OaEnthalpy
. Refer to the CARE User’s Manual form, 74-5587 for information on creating global points in Excel
5000 controllers.
ADDING OTHER VOLTAGE/CURRENT SENSORS
See Table A-1 for the supported Voltage/Current analog input sensors that can be connected to the RIO Device. The user
must add a software point (pseudo analog - in RIO CARE Plant) that can be mapped to the actual hardware input (RIO Plant)
through the Custom Mapping function of E-Vision. The procedure described previously for adding an enthalpy ( 4 to 20 mA)
sensor should be followed and instructs the user on adding the pseudo analog point in the RIO CARE Plant and using the