EXCEL 10 W7761A INPUT/OUTPUT DEVICE
41
74-2699
Custom Mapping function. From there it can be used with other Excel 10 controllers (referenced) on the E-Bus, that are used in
the Zone Manager control strategy or switching logic, or are used with Excel 5000 controllers on the C-Bus.
Table A-1. Supported Voltage And Current Input Sensors.
E-Vision Enumerated Name in the Input
Application Selection Tab
RIO Network Variable that contains the
Hardware Input Value
RA_Hum_C7600C
Humidity1 or Humidity2
OA_Hum_C7600C
Humidity1 or Humidity2
Filter_Diff_Pres
Pressure1 or Pressure2
RA_Hum_C7600B
Humidity1 or Humidity2
OA_Hum_C7600B
Humidity1 or Humidity2
RA_Enthalpy
CurrentAI
OA_Enthalpy
CurrentAI
Space_CO2
CO2Level
Voltage_Monitor
VoltageAI
ADDING DIGITAL INPUTS
See Table A-2 for the supported Digital input types that can be connected to the RIO Device. The user must add a software
point (pseudo digital nstate - in RIO CARE Plant) that can be mapped to the actual hardware input (RIO Plant) through the
Custom Mapping function of E-Vision. The procedure described previously for adding an enthalpy ( 4 to 20 mA) sensor should
be followed. The user will add a 
Pseudo Digital nstate point
 (<
Vd
>) in step one instead of the Pseudo Analog to the RIO CARE
Plant and then use the Custom Mapping function. From there it can be used with other Excel 10 controllers (referenced) on the
E-Bus, that are used in Zone Manager control strategy or switching logic, or are used with Excel 5000 controllers on the C-Bus.
Table A-2. Supported Digital Input Types.
E-Vision Enumerated Name in the Input
Application Selection Tab
RIO Network Variable that contains the
Hardware Input Value
Digital Input 1:
Active_Short / Active_Open
SrcDigIn1Sts
Digital Input 2:
Active_Short / Active_Open
SrcDigIn2Sts
Digital Input 3:
Active_Short / Active_Open
SrcDigIn3Sts
Digital Input 4:
Active_Short / Active_Open
SrcDigIn4Sts
ADDING DIGITAL OUTPUTS
See Table A-3 for the supported digital output types that can be connected to the RIO Device.
The user must add a software point (pseudo analog) that can be mapped to the actual hardware output through the Custom
Mapping function of E-Vision. The following procedure will instruct the user on adding the pseudo analog and using the Custom
Mapping function so that the Digital Output can be used in the Zone Manager control strategy or switching logic, or be used
with Excel 5000 controllers on the C-Bus.
1. With CARE running, open an existing RIO plant. The user can go into either switching logic or control strategy to add the
pseudo analog point. If the user does not have an existing control loop through control strategy, use switching logic to
add the pseudo point, otherwise a control loop will have to be created along with unnecessary RACL to add the point.
This procedure will use switching logic to add the pseudo analog point. With the RIO plant having the focus, go into
switching logic. Select the 
Software Points
 menu item and then 
Pseudo Analog
. The 
Create/Select Software Point
 <
Va
>
dialog box will be displayed. Type in a New point name for the Digital Output (such as 
MiscExhFan
) and click on the 
OK
button. The new point that was just created will be added to the screen as the header point for switching logic table and
also added to the 
Point
 list. Select the 
Cancel
 button to exit the 
Create/Select Software Point
 <
Va
> dialog box. Exit
switching logic by selecting the 
File
 menu item and 
Exit
. CARE will display the 
Delete Unused Software Points
 list box.
Click the 
Cancel
 button to continue.
2. Go into the 
Data Point Editor
 (
Controller/Edit/Data Point Editor
) and under 
Point
 select the pseudo analog point that was
just created and the 
OK
 button. Select the drop down list for the 
Engineering Unit
 and scroll through the list until the 
Pct
engineering units
 are displayed. Select the Pct engineering unit that is shown with one decimal place (number 55) and
the 
OK
 button to save the selection. 
Cancel
 the 
User Address
 list box and select 
File/Exit
 to exit out of the 
Data Point
Editor
.
3. Translate the Zone Manager and Export the Zone Manager files to E-Vision by selecting the 
Project
 and 
Export
 to E-
Vision menu items. Type in the name of the Zone Manager Export file when the 
Export Zone Manager
 dialog box is