Lg Electronics 120S 사용자 설명서

다운로드
페이지 306
Chapter 8  Communication Functions 
8-63 
 
 
• S3 format is as below. 
 
                bit 15                                                                              bit 8                                                            bit 1      bit 0 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
• NDR : when the communication ends normally, this bit turns on during 1 scan. 
• Error bit : when communication error occurs, this bit turns on during 1 scan. At that time error code stores bit 8 ~ bit 15.   
• Error code is as follow 
 
Code 
Error type 
Meaning 
01 
Illegal Function 
Error in inputting function code in instruction. 
02 
Illegal Address 
Error of exceeding the area limit of reading/writing on the slave station. 
03 
Illegal Data Value 
Error when the data value to be read from or write on the slave station isn’t 
allowed. 
04 
Slave Device Failure 
Error status of the slave station. 
05 Acknowledge 
It’s a responding code of the slave station for the master station to prevent the 
master station time-out error, when request command processing takes time. 
The master station marks an error code and waits for a certain time without 
making any second request. 
06 
Slave Device Busy 
Error when request command processing takes too much time. The master 
should request again. 
07 Time 
Out 
Error when exceeds the time limit of the communication parameter as it 
communicates. 
08 
Number Error 
Errors when data is 0 or more than 256 bytes   
09 
Parameter Error 
Error of setting parameters (mode, master/ slave) 
10 Station 
Error 
Error when the station number of itself and the station number set by the 
S1 of instruction are the same. 
 
 
 
 
 
 
 
Error bit 
NDR bit
Error code 
Remark 
 
-. In MASTER-K120S series, the ‘MODBUS’ command which has been used in MK80S series can be used.   
In this case, communication channel is fixed to channel 0.