Chapter 8  Communication Functions 
8-64 
 
 
2) Example program 1 
It’s supposed that MASTER-K120S main unit is the master and it reads Coil Status of the station no. 17, a Modicon product. 
The master reads status of the Coil 00020 ~ 00056 of the slave station no. 17. The Coil of the slave station is supposed to 
be as follows and the data that are read is saved in D1000 
 
Coil 
59  58  57  56  55  54
53
52
51
50
49
48
47
46
45  44  43  42  41
40
Status 
X  X  X  1 
0
1
1
0
0
0
0
1
1
1
1
Hex 
 
1 B 0 E B 
Coil 
39  38  37  36  35  34
33
32
31
30
29
28
27
26
25  24  23  22  21
20
Status 
1
1
0
1
0
1
1
1
1
0
1
Hex  
 
             
• The status of Coil 57, 58, 59 are redundancy. 
• Data is sent starting from the low bit by byte unit. If the deficient bit of a byte is filled with 0. An example of sending the 
above data is as Following example 1. 
Example 1)    CD B2 0E 1B 
                  ① It designates slave station and function code (No. of station : h11(17) , function code : h01) 
                  ② Address setting 
            - Address ‘0’ at MODBUS protocol means address ‘1’ actually .So if you want to designate address ‘20’ , write   
address ‘19’ 
                  ③ Reading number setting ( Reading number is 37 from 20 to 56.) 
                  ④ This is MODBUS Communication instruction. 
- Data is sent starting from the low bit by byte unit. If the deficient bit of a byte is filled with 0. An example of sending   
the above data is as follows. 
                        - The data transmission starts lower byte. The remnant part of byte is filled with ‘0’ 
⑤ 
Stored data at D1000,D1001,D1002 are : 
 
Device 
Stored data 
D1000 
h  CD  6B 
D1001 
h  B2  CE 
D1002 
h  00  1B