314 VT1422A Command Reference  
OUTPut
Returned Value: Numeric value of amplitude set. The data type is float32.
Related Commands: OUTP:CURR:AMPL
Send with VXIplug&play Function: hpe1422_cmdReal64_Q(...)
Usage
OUTP:CURR:AMPLITUDE?  (@163)
Check SCP current set for channel 63 
(returns +3.0E-5 or +4.88E-4)
OUTPut:CURRent[:STATe]
OUTPut:CURRent[:STATe] <enable>,(@<ch_list>) 
enables or disables current 
source on channels specified in <ch_list>.
Parameters
Comments
OUTP:CURR:STAT does not affect a channel's amplitude setting. A channel 
that has been disabled, when re-enabled sources the same current set by the 
previous OUTP:CURR:AMPL command.
OUTP:CURR:STAT is most commonly used to turn off excitation current to 
four-wire resistance (and resistance temperature device) circuits during 
execution of CAL:TARE for those channels.
When Accepted: Not while INITiated
Related Commands: OUTP:CURR:AMPL, CAL:TARE
*RST Condition: OUTP:CURR OFF (all channels)
Send with VXIplug&play Function: hpe1422_cmd(...)
Usage
OUTP:CURR OFF,(@100,108)
turn off current source channels 0 and 8
Parameter
Name
Parameter
Type
Range of
Values
Default 
Units
enable
boolean (uint16)
1 | 0 | ON | OFF
none
ch_list
channel list (string)
100 - 163
none