SITRANS LR 460 – INSTRUCTION MANUAL
7ML19985JM01
mmmmm
S
IMA
T
IC PD
M
D/A (Digital/Analog) Trim
Allows you to trim the 4 mA and 20 mA points in order to calibrate the mA output. 
Open the menu Device – D/A Trim. You will be prompted to attach a calibrated meter and 
enter the values at 4 mA and at 20 mA. 
Simulate AO (Analog Output)
Allows you to input a simulated value in order to test the functioning of the mA 
connections during commissioning or maintenance of the device.
To simulate a user-defined mA value:
1. Open the menu Device – Simulate AO. 
2. Select Other, enter the new value, and click OK. The message ’Field Device fixed 
at new value’ appears. Click OK.
3. When you are ready to end simulation, select End and click OK to return the 
device to the original output level.
Simulation
Simulate Analog Input to AIFB1 or AIFB2
Allows you to input a simulated value in order to test the functioning of the Analog Input 
Function Blocks.
1. Open the menu Device – Simulation, and select the desired function block.
2. Enable simulation, enter a value, and click Transfer.
3. After simulation is complete, disable simulation.
Simulate Input
Allows you to simulate the sensor value which is input to the Level Transducer Block. This 
tests everything between the Level Transducer Block and Output.
1. Open the menu Device – Simulation, and select Simulation (Input).
2. To enable simulation select Fixed or Ramp.
If you select Ramp, enter the step length and number of steps. 
3. Enter the simulated value and click Transfer.
4. After simulation is complete, disable simulation.
Note: 
The Simulation parameter influences output to the control system.