SITRANS LC  500 – INSTRUCTION MANUAL
7ML19985GE01
mmmmm
Int
er
connect
ion
Upper and Lower Threshold, (menus 13 and 14) and the accompanied delays (menus 15 
and 16). 
Initially the solid-state output is disabled for both signal output and fault/failure output 
(menu 17). When the solid-state switch is to be operated as fault/failure output (for 
example, for a separate shutdown system), we recommend disabling the operation for 
signal output (select Disabled Mode in menu 17 on page 70). There is no delay in the 
operation for fault/failure output. 
Switch Protection (Diode)
Factory Settings
The SITRANS LC 500 has a number of default factory settings. If the required settings for 
the application are known, the settings can be modified during final testing.
Settings:
Notes: 
The solid-state output should only be used in circuits where the current is limited 
by a proper load.
Due to the limited switching capabilities of the solid-state switch component, an 
auxiliary relay must be applied when switching high-current/high-voltage 
apparatus. 
WARNING: When the solid-state switch is activating an external 
relay, protection diodes must be connected in the correct polarity 
across the relay coil to prevent possible switch/relay damage 
resulting from inductive spikes generated by the relay coil.
Note: 
To restore factory settings, use menu item 12 (see 
for details).
Setting
Description
ID
Has a unique serial number
TV0   Units
PF
TV0   UL
3300 pF [switch position (0)C]
TV0   LL
1.666 pF [switch position (0)B]
TV0   URV
3300 pF [switch Position (0)F]
TV0   LRV
0.00 pF [switch Position (0)E]
AO1
4-20 mA is 0-100% [position (0)8]
TAG
"customer input data via HART"
DESCRIPTOR
"customer input data via HART"
MESSAGE
"Siemens Milltronics P I"