ventilation air by one of the methods described in the National Fuel 
Gas Code, ANSI Z223.1, Section 5.3. or applicable local codes.
Example of Large Room with 1/2 Wall divider.
Figure 1
The following formula can be used to determine the maximum heater 
rating per the definition of unconfined space:
Btu/Hr = 
(L
1
 + L
2
)FT x (W)FT x (H)FT
     x 1000
50
If the area in which the heater may be operated is smaller than that defined 
as an unconfined space, provide adequate combustion and ventilation air 
by one of the methods described in the National Fuel Gas Code, ANSI 
Z223.1, Section 5.3.
Adhere  to  all  codes,  or  in  their  absence,  the  latest  edition  of  THE 
NATIONAL FUEL GAS CODE ANSI Z223.1 or NFPA54 which can be 
obtained from:
 
American National Standards Institute National Fire Protection Association, Inc.
 
11 West 42nd St. 
Batterymarch Park
 
New York, NY 10018 
Quincy, MA 02269
Minimum  Dimensions  For  Solid  Fuel  Burning  Fireplaces 
UL127 Factory Built Fireplaces (Figure 2)
Model
A
B
C
D
VFDR18
17"
12"
28"
17"
VFDR24
23"
12"
30"
18"
VFDR30
26"
12"
34"
20"
The dimensions shown and defined in the fireplace manufacturer’s 
instructions are minimum clearances to maintain in installing this 
heater. Left and right clearances are determined when facing the 
front of the heater.
Glass Doors
Make sure that glass doors are open during all operations of 
the  logset.  The  opening  of  the  glass  door  frame  should  be 
the  dimension  used  for  the  minimum  front  opening  of  the 
firebox.
Follow these instructions to ensure safe installation.
Failure to follow instructions exactly can create a fire hazard.
Figure 2
This heater shall not be installed in a confined space unless provi-
sions are provided for adequate combustion and ventilation air.
The National Fuel Gas Code defines a confined space as a space 
whose volume is less than 50 cubic feet per 1,000 Btu per hour 
(4.8m
3
  per  kw)  of  the  aggregate  input  rating  of  all  appliances 
installed in that space and an unconfined space as a space whose 
volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m
3
 
per kw) of the aggregate input rating of all appliances installed in 
that space. Rooms communicating directly with the space in which 
the appliances are installed, through openings not furnished with 
doors, are considered a part of the unconfined space.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough 
fresh air for combustion and ventilation. However, in buildings of 
unusually  tight  construction,  you  must  provide  additional  fresh 
air.
  Unusually  tight  construction  is  defined  as  construction 
where:
a.  Walls and ceilings exposed to the outside atmosphere have 
a continuous water vapor retarder with a rating of one perm 
or less with openings gasketed or sealed, and
b.  Weather-stripping has been added on openable windows and 
doors, and
c.  Caulking  or  sealants  are  applied  to  areas  such  as  joints 
around window and door frames, between sole plates and 
floors, between wall-ceiling joints, between wall panels, at 
penetrations for plumbing, electrical, and gas lines, and at 
other openings.
  If your home meets all of the three criteria above, you must 
provide additional fresh air. 
Warning: If the area in which the heater may be operated is smaller 
than that defined as an unconfined space or if the building is of 
unusually  tight  construction,  provide  adequate  combustion  and 
PROVISIONS FOR ADEQUATE COMBUSTION & VENTILATION AIR