Use the arrow buttons to change the contrast value 
(range is 00 to 37). Pressing the “HOME” button 
while in edit mode will return the value to the last 
entered value. 
Press the “ENTER” button to exit edit mode.
The contrast is now set and can only be changed by 
editing the value on this page.
ENABLE GENERAC COMMERCIAL 
TRANSFER SWITCH (HTS)
The H-100 Control Panel can control up to four HTSs 
via the RS-485 communications port. The H-100 
Control Panel is shipped without the HTS control 
enabled. If the user has an HTS in their system, they 
must enable the HTS via GenLink or the front panel. 
If the HTS is not enabled, the generator will not 
operate automatically with loss of utility. If the H-100 
Control Panel enables a non-existent HTS, there will 
be a warning indicated. 
NOTE:
Non-HTS switches use the two-wire start inter-
face and do not need enabling by H-100 Control 
Panel.
HTS SETUP USING GENLINK
Connect to the H-100 control panel.
Using the “Configuration” pull down, select “Transfer 
Switch Configuration” to display the HTS Configuration 
screen.
‹
The lower left corner contains the HTS number. Use 
the “Prev” and “Next” buttons to select the appro-
priate switch number - 1 through 4. If enabling the 
switch, check the “Switch Connected” check box 
in the middle of the screen. If disabling the switch, 
uncheck the “Switch Connected” check box. The 
remainder of the settings on this page are described 
in the HTS manual.
HTS SETUP USING FRONT PANEL
Press the “MENU” button.
‹
General Information
H-100 Control Panel Technical Manual