Generac Power Systems H-100 사용자 설명서

다운로드
페이지 52
INTRODUCTION
The H-100 Control Panel is an electronic control box 
that functions as an advanced standby generator 
controller. Its technology is based on the flagship PM-
DCP system with all its flexibility included. A familiar 
user interface in the form of GenLink®-DCP is used 
to program, monitor and change the parameters in 
the unit. The interface appears the same as it does 
for the PM-DCP.
Specialized programs are built into the H-100 Control 
Panel to allow customers to configure spare I/O to 
their own needs. For example, built in Integrated 
Logic Controller (ILC) logic can eliminate the need 
for ancillary external controllers. Everything can be 
user customized from measurements to alarms to 
the screen displays.
Why do we do this? Having one set of control firm-
ware buys us the economy of scale which can be 
passed on to the customer. It also has great technical 
advantages. The H-100 Control Panel and all PM-DCP 
products are built around a common “core” of firm-
ware. This provides EVERY product with the same 
technical tools. For example, both the H-100 Control 
Panel and PM-DCP products can call out for assis-
tance via a modem, every product can provide trend-
ing data for its measured parameters, any measured 
value can be setup to create alarms or warnings, each 
product has a built in ILC, etc. H-100 Control Panel 
is very flexible.
FEATURES
Local/remote connection to a PC for GenLink®-
DCP communication.
Interface with up to four Generac Commercial 
Transfer Switches (HTS).
Interface with up to two Remote Annunciator 
Panels.
Customizable display.
New Generation GenLink.
Built-in Frequency and Voltage controller. 
External modem option with dialout capability 
upon alarm.
Communication via standard CAN bus and Modbus 
protocols.
Programmable I/O channel properties.
Programmable alarm/warnings.
Alarm and event logging with time stamping.
Parameter logging and trending both to file and 
graphical.
Built-in diagnostics.
Internal ILC for combinatorial logic functions 
including analog inputs.
Spare customer programmable Analog input capac-
ity.
Spare customer programmable Digital I/O capac-
ity.
Firmware can be updated via Telephone line.







PANEL SETUP
 CHANGING THE CONTROLLER 
CONFIGURATION
The H-100 Control Panel controller is setup in the 
factory to match the product it is shipped with and 
generally no changes are required. For spares pur-
poses the controller can be re-configured in the field 
using the GenLink software tool and a PC.
If you need to change the function of the panel the 
best way to get a basic setup for a product is to use 
GenLink to download a “product file”. This will setup 
all the basic parameters and just leave customization 
and calibration to be done. Product files are available 
on the web site for downloading cross referenced to 
product serial numbers/generic product types. The 
manufacturer does not recommend changing the 
settings individually for a product as this is labori-
ous and prone to human error. Some of the settings 
require detailed knowledge of things like governor 
settings which are not easily discernable.
Some configurations are changeable from the H-100 
Control Panel touch pad and displays. These configu-
rations will be described later and include:
Setting Display Contrast
Setting System Time and Date
Setting up/Enabling Internal Exercise
Enabling Interface with Generac Commercial 
Transfer Switch (HTS)
CUSTOMIZATION
The controller is designed to be very flexible and 
allow great levels of customization via the GenLink 
tool. Once you have customized your controller, you 
should save the settings away to floppy or hard disk 
for backup. This can be done during the customiza-
tion process, or at any time subsequent to customiza-
tion by uploading the settings from the controller to 
GenLink and then saving them to disk. The digital 
outputs can be set to turn on from any one of a list 
of functions, or they can be used as part of the built-
in ILC. The digital inputs can be moved, inverted, 
renamed, given delay times, made alarms, used 
in the ILC, logged/not logged, etc. Refer to the sec-
tion “MEASUREMENT ENGINE” for details. Analog 
inputs are dealt with in the same section.
There are some parameters which are specific to the 
product, such as an engine controller or transfer 
switch. These are all customizable via GenLink. Refer 
to the relevant section for details.
‹



‹
General Information
H-100 Control Panel Technical Manual
 2