THE MEASUREMENT "ENGINE"
The measurement “engine” is the key feature of the 
system. All the inputs to the controller are processed 
by this module. Each physical input is measured and 
the result processed by an individual set of rules that 
are set via a PC and GenLink. Normally, a product 
is delivered with the inputs and outputs pre-con-
figured and nothing needs to be done, however the 
manufacturer has provided complete flexibility to 
each measurement (except where product safety is 
concerned). The inputs are divided into analog and 
digital channels.
ANALOG CHANNELS
There are 23 analog channels of which 14 have fixed 
functions. The remaining 9 channels are split between 
product specific inputs (such as oil temperature), 
and customer spares. The exact split depends on the 
product. Table 1 shows the channel allocation.
Some of the 14 fixed channels are “DERIVED” read-
ings in that they are calculated from the other read-
ings. For example, power is calculated from both volt-
age and current. These are not real hardware chan-
nels, but they result in an analog reading that can be 
treated as a “fixed channel” just like any other.
‹
ANALOG MATHS
Each of the 23 channels is processed by a set of mea-
suring rules using constants that are set via GenLink. 
Usually these constants can be changed by the cus-
tomer. In the following illustration, the measurement 
is represented by M and the GenLink constants are 
in italics. The measurement is processed in the fol-
lowing order and the result is then stored for cus-
tomer display or use.
M = M * Calibration Factor
This is used to calibrate out any reading inaccura-
cies where calibration factor is a number such that 
1024 is equivalent to 1, so it’s really M * calibration 
factor/ 1024. GenLink will hide this computation so 
you can enter floating point numbers such as 1.1 or 
0.987 etc.
THEN
M = M processed by function x:
‹
General Information
H-100 Control Panel Technical Manual
 CPU
 Channel 
 
 
Derived
 
No. 
Channel Title 
Update Rate 
Value
 
User Configurable #1 (Usually Oil Temp) 
3.84 ms 
No
 
User Configurable #2 (Usually Coolant Temp) 
3.84 ms 
No
 
User Configurable #3 (Usually Oil Pressure) 
3.84 ms 
No
 
10 
User Configurable #4 (Usually Coolant Level) 
3.84 ms 
No
 
11 
User Configurable #5 (Usually Fuel level) 
3.84 ms 
No
 
12 
User Configurable #6 - Spare - 
3.84 ms 
No
 
13 
User Configurable #7 (Usually throttle position) 
3.84 ms 
No
 
14 
Special Oxygen sensor 
3.84 ms 
No
 
15 
Special Battery charge sensor 
3.84 ms 
No
 
16 
Battery Voltage/ PSU voltages 
3.84 ms 
No
 
Generator Phase A RMS Current 
Phase A ZERO CROSSING 
No
 
Generator Phase B RMS Current 
Phase B ZERO CROSSING 
No
 
Generator Phase C RMS Current 
Phase C ZERO CROSSING 
No
 
Generator average current 
Every Phase ZERO CROSSING 
Yes
 
Generator Phase A RMS Voltage 
Phase A ZERO CROSSING 
No
 
Generator Phase B RMS Voltage 
Phase B ZERO CROSSING 
No
 
Generator Phase C RMS Voltage 
Phase C ZERO CROSSING 
No
 
Generator average voltage 
Every Phase ZERO CROSSING 
Yes
 
Total Generator Power KW 
Every Phase ZERO CROSSING 
Yes
 
Total Generator Power Factor 
Every Phase ZERO CROSSING 
Yes
 
Generator Frequency 
Every Phase ZERO CROSSING 
Yes
 
RPM #1 
4 - 8 ms variable (geared) 
Yes
 
Oxygen sensor zero crossings 
Every O2 ZERO CROSSING 
No
Table 1