Generac Power Systems H-100 사용자 설명서

다운로드
페이지 52
H-100 CONNECTOR PIN DESCRIPTIONS
 J1  Wire 
Signal 
Description 
J2 
Wire 
Signal 
Description
 
 
CAN (rtn) 
CAN Bus 
391 
RS485 (-) 
Diagnostic/Rem-An/HTS
 
 
CAN (+)  
CAN Bus (+) 
388 
RS232 (tx)  
GenLink
 
810 
Gnd 
Modem Power (-) 
IN7 
IN (DB) 7 
DI-3/Line Power
 
805 
AN8 (rtn)  
Emissions Sensor/ 
183 
IN (DB) 4 
Remote Start
 
   
Fluid 
Basin 
Level
 
804 
AN8 (+) 0-1V 
Emissions Sensor/ 
174 
IN (DB) 1 
Key Switch in AUTO
 
   
Fluid 
Basin 
Level
 
575R 
AN5 (rtn) 
Fuel Level 
224 
Vsense 1 
Phase AB Voltage
 
575V 
AN5 (+) 4-20mA 
Fuel Level 
227 
Gnd 
Vsense PCB Ground
 
523R 
AN1 (rtn)  
Oil Temperature 
403 
OUT (OC) 14 
AVR Gate trigger ‘B’
 
523V 
AN1 (+) 4-20mA 
Oil Temperature 
399C 
CT3 (-) 
Phase C Current
  10 
R15B 
OUT (OC) 10 
Overspd Shutdown 
10 
398C 
CT3 (+) 
Phase C Current
  11 
256 
OUT (OC) 2 
Fuel Relay 
11 
399A 
CT1 (-) 
Phase A Current
  12 
- Batt (12/24V) 
Panel Power (-) 
12 
398A 
CT1 (+) 
Phase A Current
  13 
 
CAN (-) 
CAN Bus (-) 
13 
390 
RS485 (+) 
Diagnostic/Rem-An/HTS
  14 
811 
IN (DB) 9 
Modem DCD 
14 
387 
RS232 (rx)  
GenLink
  15 
68V 
AN2 (+) 4-20mA 
Coolant 
15 
567/601 
IN (DB) 6 
DI-2/Ruptured Basin/
 
   
Temperature 
    
Low 
Fuel 
Pressure
  16 
803 
AN9(+) 0-5V 
Battery Charger Cur 
16 
R15 
IN (DB) 3 
Emergency Stop
  17 
766R 
AN7 (rtn) 
Throttle Position 
17 
226 
Vsense 3 
Phase CA Voltage
  18 
766V 
AN7 (+) 4-20mA  
Throttle Position 
18 
 
+12V (500 mA) 
Vsense PCB
  19 
69R 
AN3 (rtn) 
Oil Pressure 
19 
405 
Gnd 
AVR PCB Power (-) 
  20 
69V 
AN3 (+) 4-20mA  
Oil Pressure 
20 
404 
OUT (OC) 13 
AVR Gate trigger ‘A’
  21 
221/808 
OUT (OC)12 (PWM) 
Preheat/Air 
21 
OC8 
OUT (OC) 8 
Auxiliary 4 Output
 
   
/Fuel 
Solenoid
  22 
242 
OUT (OC) 4 
13.3 Gas Relay  
22 
OC6 
OUT (OC) 6 
Auxiliary 2 Output
  23 
56A 
OUT (OC) 1 
Starter Relay 
23 
OC5 
OUT (OC) 5 
Auxiliary 1 Output
  24 
0/shld 
RPM sensor (-)  
Engine RPM 
24 
SHLD 
RS485 (shield)  
Diagnostic/Rem-An/HTS
  25 
79 
RPM sensor (+) 
Engine RPM 
25 
389 
RS232 (com)  
GenLink
  26 
812 
IN (DB) 10 
Modem Enable 
26 
IN8 
IN (DB) 8 
DI-4/Generator Power
  27  AI1R/806/ 
AN6 (rtn) 
Fuel Press/Ign. Alarm/ 
27 
505 
IN (DB) 5 
DI-1/Battery Charger Fail
 
 754R  
Inlet 
Temp
  28 
AI1S/ 
AN6 (+) 4-20mA 
Fuel Press/ 
28 
175 
IN (DB) 2  
Key Switch in MANUAL
 
 754V  
Inlet 
Temp
  29 
573R 
AN4 (rtn) 
Coolant Level 
29 
225 
Vsense 2 
Phase BC Voltage
  30 
573V 
AN4 (+) 4-20mA  
Coolant Level 
30 
406 
AVR Zero Crossing  
AVR Zero Crossing Input
  31 
68R 
AN2 (rtn) 
Coolant Temp 
31 
194 
+12V (300 mA) 
AVR PCB Power (+)
  32 
809 
+12V (300mA) 
Modem Power (+) 
32 
OC9/25 
OUT (OC) 9 
13.3 Ignition Power
  33 
769 
OUT (OC)11 (PWM) 
Throttle Driver 
33 
OC7 
OUT (OC) 7 
Auxiliary 3 Output
  34 
445 
OUT (OC) 3 
Fault Relay 
34 
399B 
CT2 ( - ) 
Phase B Current
  35 
15B/220B 
+ Batt ( 12/24V ) 
Panel Power ( + ) 
35 
398B 
CT2 ( + ) 
Phase B Current
‹
KEY:
OUT (O/C) #1-14  =   Digital OUTput, Open Collector (includes 
PWM Outputs, AVR Gates) 
IN (DB) #1-10 
=   Digital INput, Buffered (Schmitt Trigger) 
“Pulled up”
AN #1-7 (+) 
 =  Analog 12V ( 50 mA ) source
AN #1-7 (rtn) 
 =  General purpose analog input ( 4 - 20 mA )
Vsense #1-3 
 =  Voltage sensing input ( 0 - 28.8 VAC)
CT #1-3 
=  Current Transformer input ( 0 - 3 A AC)
 46
Appendix B
H-100 Control Panel Technical Manual