  Number 
Default Function Name 
Function Description
 
63 
BAT VOLT LO WARN   
Battery Voltage has gone below maximum warning limit
 
64 
AVG CURR HI ALRM 
Average Current has gone above maximum alarm limit
 
65 
AVG CURR LO ALRM 
Average Current has gone below minimum alarm limit
 
66 
AVG CURR HI WARN 
Average Current has gone above maximum warning limit
 
67 
AVG CURR LO WARN 
Average Current has gone below maximum warning limit
 
68 
AVG VOLT HI ALRM 
Average Voltage has gone above maximum alarm limit
 
69 
AVG VOLT LO ALRM 
Average Voltage has gone below minimum alarm limit
 
70 
AVG VOLT HI WARN 
Average Voltage has gone above maximum warning limit
 
71 
AVG VOLT LO WARN 
Average Voltage has gone below maximum warning limit
 
72 
TOT PWR HI ALARM 
Total Real Power has gone above maximum alarm limit
 
73 
TOT PWR LO ALARM 
Total Real Power has gone below minimum alarm limit
 
74 
TOT PWR HI WARN 
Total Real Power has gone above maximum warning limit
 
75 
TOT PWR LO WARN 
Total Real Power has gone below maximum warning limit
 
76 
GEN FREQ HI ALRM 
Generator Frequency has gone above maximum alarm limit
 
77 
GEN FREQ LO ALRM 
Generator Frequency has gone below minimum alarm limit
 
78 
GEN FREQ HI WARN 
Generator Frequency has gone above maximum warning limit
 
79 
GEN FREQ LO WARN 
Generator Frequency has gone below maximum warning limit
 
80 
GEN FREQ FAULT 
Generator Frequency exceeds nominal limits for valid sensor reading
 
81 
ENG RPM HI ALARM 
Engine RPM has gone above maximum alarm limit
 
82 
ENG RPM LO ALARM 
Engine RPM has gone below minimum alarm limit
 
83 
ENG RPM HI WARN 
Engine RPM has gone above maximum warning limit
 
84 
ENG RPM LO WARN 
Engine RPM has gone below maximum warning limit
 
85 
ENG RPM FAULT 
Engine RPM exceeds nominal limits for valid sensor reading
 
86 
SWITCH IN AUTO 
Key Switch in AUTO digital input active
 
87 
SWITCH IN MANUAL 
Key Switch in MANUAL digital input active
 
88 
E-STOP ACTIVE 
Emergency Stop Status digital input active
 
89 
REMOTE START ACT 
Remote Start digital input active
 
90 
DIG INPUT 05 ACT 
DI-1, Digital Input #5 active
 
 
BATT CHARGE FAIL 
Battery Charger Fail digital input active
 
91 
DIG INPUT 06 ACT 
DI-2, Digital Input #6 active
 
 
RUPTURED BASIN 
Ruptured Basin digital input active,
 
 
PROP LEAK ACT 
Propane Gas Leak digital input active,
 
 
LOW FUEL PRS ACT 
Low Fuel Pressure digital input active
 
92 
DIG INPUT 07 ACT 
DI-3, Digital Input #7 active
 
 
LINE POWER ACT 
Line Power digital input active
 
93 
DIG INPUT 08 ACT 
DI-4, Digital Input #8 active
 
 
GEN POWER ACT 
Generator Power digital input active
 
94 
DIG INPUT 09 ACT 
Digital Input #9 active
 
 
MODEM DCD ACT 
Modem Carrier Detect digital input active
 
95 
MODEM ENAB ACT 
Modem Enable digital input active
 
96 
ILC ALR/WRN #1 
ILC controlled: ILC warning or alarm signal # 1
 
97 
ILC ALR/WRN #2 
ILC controlled: ILC warning or alarm signal # 2
 
98 
IN WARM UP 
Generator is running, but not fully warmed up yet
 
99 
IN COOL DOWN 
Generator is running, but cooling down before shutting off.
 
100 
CRANKING 
Generator is starting – the starter is engaged
 
101 
NEED SERVICE 
Maintenance item has expired
 
102 
SHUTDOWN GENSET 
Shutdown alarm is active
Appendix B
H-100 Control Panel Technical Manual