and reduce the stack gas temperature loss. Insulation may be added around the liner for further 
temperature stability. If the chimney is on the home's exterior or passes through a sizable, unheated area 
of the building, such as a porch, high ceiling attic, etc., and condensing occurs, the chimney must be 
insulated around its exterior to help the flue hold its temperature. Also, check to see if the chimney is too 
large for the furnace and other appliances connected to it. If so, reduce to proper size (see Appendix E of 
NFPA31) by lining. Be sure to use stainless steel liners, such as stainless types 430, 304, or for the 
toughest corrosion problems, type 316. If the chimney is the correct size for the unit and condensing still 
occurs, then insulating the vent connector and/or reducing the efficiency of the furnace may have to be 
done to raise the chimney temperature. 
 
More detailed information may be obtained from the latest edition of the ASHRAE HVAC Systems and 
Equipment Handbook. 
 
3. PROPER CHIMNEY HEIGHT: 
The chimney shall terminate at least 3 feet above the highest point where it passes through the roof of a 
building and at least 2 feet higher than any portion of a building within a horizontal distance of 10 feet. 
(See Fig. 2a). 
                           
 
Fig. 2: Proper chimney termination height for pitched roofs 
 
If the chimney penetrates a roof more than 10 feet from a ridge, wall or parapet, a minimum of 3 feet 
above roof or exit point must be maintained.  See Figure 2b. 
 
If the roof is flat rather than the normal residential pitched roof, refer to Figure 3 for proper clearances. 
 
Fig. 3: Proper chimney termination height for flat roofs 
 
4. PROPER VENT CONNECTOR PIPE/CHIMNEY CONNECTION: 
The vent connector pipe should extend only to (and not beyond) the inside wall of the chimney (See Fig. 
4). A thimble should be used to connect the vent connector pipe to the chimney so that the vent 
connector pipe may be readily removed in case of inspection or replacement.