Thermo Products OD6FX072DV5R 사용자 설명서

다운로드
페이지 76
 
  5 
 
II.  GENERAL INSTRUCTIONS - READ BEFORE START OF INSTALLATION 
 
1.  The heating output capacity of the furnace proposed for installation should be based on a heat loss 
 calculation made according to the manuals provided by the Air Conditioning Contractors of America 
(ACCA) or the American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc. 
(ASHRAE). 
 
2.  All local codes and/or regulations take precedence over the instructions in this manual and should be 
followed accordingly. In the absence of local codes, installation must conform with these instructions and 
regulations of the National Fire Protection Association, and to the provisions of the National Electrical 
Code (ANSI/NFPA 70-1999 or latest edition).  
 
3.  The installed furnace must be level and positioned in a central location with respect to outlet registers. 
It should be located near the chimney to minimize any horizontal run of flue pipe, which may be required. 
 
4.  A furnace installed in a residential garage must be installed so the burner and ignition source are 
located higher than 18 inches above the floor. The furnace must also be located or protected to avoid 
physical damage by vehicles. 
 
c
WARNING:
 This furnace is not to be used as a construction heater.  
 
5. Listed below are definitions of "COMBUSTIBLE MATERIAL" and "NON-COMBUSTIBLE MATERIAL." 
 
Combustible Material:  is made of or surfaced with wood, compressed paper, plant fibers, plastics, or 
other material that will ignite and burn, whether flame resistant or not. 
 
Non-Combustible Material:  is material that is not capable of being ignited and burned.  Such materials 
consist entirely of, or a combination of, steel, iron, brick, tile, concrete, slate, or glass.   
 
Table 1:  MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS 
 
TYPE OF 
UNIT 
MODEL NO.
1
 
FROM 
SIDES OF 
FURNACE 
FRONT 
TOP & 
SIDES OF 
PLENUM 
FROM THE 
FLUE/VENT 
REAR 
Counterflow / 
Horizontal 
OD6F*072D*** 0” 
Note 
1
 1” 
7”  0” 
Counterflow / 
Horizontal 
OD6R*072D*** 0” 
Note 
1
 1” 
7”  13” 
 
 
Note:  
1
 OD6 front clearance  6” for Closet, 24” for Alcove. 
 
The minimum clearances listed in the preceding table are for fire protection.  Clearance for servicing the 
front of the furnace should be at least 24 inches.   
 
The OD6 furnaces may be installed on combustible flooring with the use of combustible floor base #D6-
BASE or a cottage base #D6COT-BASE. 
 
NOTE: The OD6 furnace is approved for closet installation. If the OD6 is installed in a closet, it requires 
two openings in the closet door for combustion air, each having a minimum area of 162 sq. inches.  This 
free area for the OD6 intentionally exceeds the recommended minimum free area of 1 square inche per 
1000 BTUH of input rate. The OD6 is also approved for attic installations. Provisions should be made for 
proper combustion air if attic is of “tight” construction.