Thermo Products OD6FX072DV5R 사용자 설명서

다운로드
페이지 76
 
 15 
 
 
 
 
 
E.  Air Filters 
 
Filter Installation 
 
The OD6 comes with (2) two 18-3/4” x 12-3/4” reusable filters. A “W” style filter rack is shipped with the 
furnace for placement of the filters inside the return air plenum.  Access to the filters is through the 
removable blower door. For horizontal installations, it is recommended that return air grill filters be 
installed for homeowner access. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Fig. 10: A typical filter rack and dimensions for the OD6 furnace. 
 
 
: Failure to comply with minimum filter installation requirements may affect the 
performance and/or void the warranty on this unit. 
 
If a method other than Thermo Pride filter racks is selected for retention of the filter and/or use of a 
different filter type is desired, refer to Table 4 below for minimum sizing guidelines for selecting filter for 
the unit.  
 
 
Model Number 
 
Filter Type 
Maximum 
Air Velocity
(ft/min) 
OD6 
*Thermo Products 
Supplied Permanent
600 
475 in² 
(2 filters @ 238in² each) 
Standard 
Permanent 
500 576 
in² 
(2 filters @ 288in² each) 
Disposable 
300 
960 in² 
(2 filters @ 480in² each) 
 
Table 4: Minimum Required Filter Area (in square inches) 
 
* The Thermo Products supplied filter can be cut to size to fit other filter retention systems as 
long as the minimum size requirement is met. 
 
NOTICE: Any internal stiffeners used in the filter must not be removed, although 
they can be cut to size as needed. 
 
19.125"
3.000"