F.  LIMIT POSITION AND LOCATION 
 
c
WARNING:  The predetermined limit locations on all of the Thermo Pride oil fired furnaces have been 
tested and approved by Thermo Products, LLC. Any attempt to relocate these safety controls or replace 
these safety controls with a control that is not approved, or is incompatible, may result in personal injury, 
substantial property damage or death. 
 
The unit listed in the table below must have the limit control installed at the time of unit installation.  
 
 
 
 
Fig. 11: Limit and auxiliary limit locations for OD6
 
 
 
MODEL DIM. 
“A” DIM. 
“B” DIM. 
“C” DIM. 
“D” 
OD6 
4-5/16” 
15” 10” 3-7/16” 
 
Table 5: Installation location of limit control and auxiliary limit control for OD6
 
 
 
G.  BURNER INSTALLATION: 
 
NOTICE:
  Remove all cardboard packing from around chamber before installing burner. 
The oil burner will mount on three stud mounting bolts on the lower mounting plate covering the opening 
in the front of the heat exchanger. The end of the burner tube should be inserted no further than 1/4 inch 
back from the inside surface of the combustion chamber. A distance further than 1/4 inch back from the 
inside chamber wall may cause impingement and sooting. This unit is equipped with a chamber retainer 
(refer to Fig.12-1 & 12-2).  For horizontal installation rotate retainer and mounting plate 90 degrees.  The 
retainer secures the chamber during shipping and helps to maintain insertion depth. DO NOT remove 
this retainer when installing burner.